9.2.1

Status byte

The status byte is a standardized code returned by a PROFIBUS slave on every bus scan, along
with the main process variable (output of the Analog Input Function Block).
• The status code indicates whether the process variable is valid or not.
• It also indicates other process-related information.
Status codes
The codes for the Status bytes are listed in the following tables. Possible causes for an error
are shown, along with measures to correct it.
If the language selected for the display is numeric, a status code will be displayed. If any
other language has been selected, a status description will be displayed.
Note
For more detail, please consult the PROFIBUS PA User and Installation Guideline (order
number 2.092), available for download from www.profibus.com (www.profibus.com).
Hex
80
84
8D
8E
A4
Set via PROFIBUS PA, in counts (see Counts in Counts (Page 88) for details).
1)
Hex
00
0F
10
Pointek CLS200/CLS300 digital
Operating Instructions, 05/2021, A5E47904060-AA
Digital
PDM display
display
_ _ _
Good
G_132
Good; Active block alarm A parameter relevant for the
G_141
Good; Active critical
alarm; Limit underflow
G_142
Good; Active critical
alarm; Limit overflow
G_164
Good; Maintenance
required
Digital
PDM display
display
---
Bad
B_015
Bad; Device failure;
Value constant
B_016
Bad; Sensor failure
Status codes for good quality
Possible cause
Normal operation
behavior of the device has
been changed. The display is
extinguished after 10 seconds.
The Sensor Value exceeds the
Lower Diagnostic Alarm Limit
1)
The Sensor Value exceeds the
Upper Diagnostic Alarm Limit
1)
Maintenance interval has
expired
Status codes for bad quality
Possible cause
Is used if no other information
is available
Device has an irreparable Error. Replace the electronics.
Sensor test failed
Remote operation
9.2 Status
Corrective measure
_ _ _
Note to the control
system
Check installation and
sensor adjustment.
Check installation and
sensor adjustment.
Maintenance work,
electronics servicing,
or sensor servicing, is
required.
Corrective Measure
Check sensor
65