4. Enter the desired output value, the quality and the status.
5. Transfer the settings to the device.
6. You can view the output behavior, for example with SIMATIC PDM (open the View Menu
Display).
7. To return to normal operation, reset the target mode to AUTO and press Transfer.
Input (Primary Value) simulation
Input Value simulation allows you to test the effects on the Primary Variable of your preset
inversion and failsafe settings, and see how the output value is affected.
Carry out the following settings:
1. Open the Device Menu Simulation
2. Select the register Input.
3. Set the simulation mode to Enabled.
4. Enter the desired input value, the quality and the status.
5. Transfer the settings to the device.
6. You can view the output behavior, for example with SIMATIC PDM (open the View Menu
Display).
7. To return to normal operation, reset the simulation mode to Disabled and press Transfer.
Sensor value simulation
By simulating the Sensor Value as a fixed value or as a parameterizable slope, you can test:
• the reaction to the Measuring Limits being exceeded
• the logic switch behavior
• the behavior of the delay timers
With a parameterizable slope you can make the simulation value dynamic. It runs from a
starting value to an end value in a step function, dwelling on each step for the preset period
of time. At the end value the direction is reversed.
Pointek CLS200/CLS300 digital
Operating Instructions, 05/2021, A5E47904060-AA
PROFIBUS PA Parameters
10.1 Measured Values
75