The figure below shows how measured values are processed within the Discrete Input
Function Block.
Discrete Input Function Block function groups
How it works
The Discrete Input Function Block allows you to control modifications to the output value
(PROFIBUS cyclic data):
• Select Inversion ON or OFF: when ON, the Primary Value from the Transducer Block, or a
simulation value given by the simulation switch, will be inverted.
• Select Failsafe behavior options: if the status of the Primary Value or Simulation Value is
bad, the fault logic can output either the last usable measured value (Mode 22 = LUv), a
given substitute value (0 or 1), or the last usable measure value with the status Bad,
sensor failure.
• Select one of 3 settings:
• The result is the output parameter (OUT).
Pointek CLS200/CLS300 digital
Operating Instructions, 05/2021, A5E47904060-AA
Setting
AUTO
MAN
O/S
Description
automatic
manual
function block disabled
Profibus PA profile structure
C.3 Description of the blocks
Output value
the automatically recorded measured
value
a manually set, fixed simulation value
the preset safety value.