7.2.1

Mode selection and adjustment

Note
Master Reset function and Condensed Status Setup are available only via SIMATIC PDM
software package.
Editing non-numerical values
• To select a mode, press M (mode key).
• To select an option in a mode, press ⇑ or ⇓ to scroll forwards or backwards through the
options. Press M to select option.
• To switch to the next mode, press M again. To cycle forwards though the menu, press M
repeatedly. To move backwards through the menu, hold M and tap ⇑.
Editing numerical values:
Numerical values are always edited from the most significant digit first, and the cursor
position is indicated by a flashing digit.
• To enable Edit function and to activate the cursor press ⇑ or ⇓.
• To increment the value of the flashing digit, press ⇑.
• To move the cursor to the right press ⇓.
• After editing the least significant digit, press ⇓ once again to store the edited value.
• To switch to the next mode, press M.
Quick reference: operating functions using input keypad
Function
Mode
#
M
Measured
value display
2)
Error display
Sensor test
2
Rise Time
4
Fall Time
5
HW Write
10
Protection
Pointek CLS200/CLS300 digital
Operating Instructions, 05/2021, A5E47904060-AA
Key function
1)
Either key activates test
Enable Edit func-
Move cursor to the
tion, or incre-
right, or store edit-
ment digit.
ed value.
Enable Edit func-
Move cursor to the
tion, or incre-
right, or store edit-
ment digit.
ed value.
Either key activates keylock.
7.2 Programming via the Local User Interface (LUI)
Display, or explanation
⇑ and ⇓
Measured value (selected in Mode 13)
Hardware or software error.
Displays GOOd or FAILd.
Time in seconds. Range: 0.0 to 100.0 s
Time in seconds. Range: 0.0 to 100.0 s
Hold for 5
– – = disabled (parameter changes al-
seconds to
lowed)
release
3)
L = enabled (parameter changes inhibit-
ed)
Local operation