Siemens Pointek CLS200 Operating Instructions Manual page 30

Hide thumbs Also See for Pointek CLS200:
Table of Contents

Advertisement

Wiring
6.2 Cable entries
5. Unscrew the middle nut (2) and visually inspect that the armour/braid has been successfully
clamped between the diaphragm seal/armour spigot and the armour clamping ring (3). If
armour/braid is not clamped, repeat assembly. (Armour/braiding should be fitted 360
degrees around the entry.)
6. Reassemble the middle nut (2) onto the entry component (5). Tighten up the middle nut (2)
until hand tight, then using a wrench, turn the nut through 1/4 turn. Tighten the backnut
(1) to form a seal around the cable, then tighten a further full turn using a wrench. Ensure
that the middle nut (2) does not rotate when tightening the backnut (1).
Note
The deluge seal on this gland locates on assembly and requires no further action. Locate
shroud over cable gland, if applicable.
Note
Switch and potentiometer settings are for illustration purposes only.
30
Alarm output solid-state switch
Test output
Sensor
Reed contact
Connect the power cable to these terminals. (Polarity is not important.)
Pointek CLS200/CLS300 digital
Operating Instructions, 05/2021, A5E47904060-AA