Remote operation

9.2 Status

Cyclic data transmission
Cyclic data transmission transfers the user data relevant for process automation between the
Class 1 Master (control or automation system) and the transmitter.
When you configure Pointek CLS200/300 on the PROFIBUS PA bus, there is one slot available
for modules, and the Level Status module is automatically inserted.
Transmission of user data via PROFIBUS PA
The user data is continuously updated by the cyclic service of PROFIBUS PA. The user data is
the OUT parameter of the Discrete Input Function Block and is composed of the Logical Level
and Status bytes.
The 2 bytes must be read consistently
by byte, and must not suffer an interrupt. If you are using an S7-300 / 400, you will need to
use SFC14 DPRD_DAT: Read Consistent Data of a Standard PD Slave.
Byte
Byte 1
Byte 2
Consistent in this context means all-at-one-time.
1)
If Condensed status is turned on (default), then the condensed status appears here.
2)
Consistent in this context means all-at-one-time.
Logical Level
The Logical Level indicates the level of the material.
Inversion
OFF
OFF
9.2
Status
Status provides information via the status byte, on the usability of the measured value in the
PLC/DCS
alarms).
Programmable Logic Controller/Distributed Control System
1)
64
Sensor Status
uncovered
covered
, the device status, and additional process information (for example, process
1)
, in a contiguous chunk: they must not be read byte
1)
Out
Logical Level
Status
2)
Operating Instructions, 05/2021, A5E47904060-AA
Logical Level
= 0 (zero)
= 1
Pointek CLS200/CLS300 digital