Parameter
Value
Reset hysteresis
State
2.10.5

Group Indications

2.10.5.1

Function Description

In the Select automation functions menu, up to 4 Group indications can be parameterized and each of
them can be assigned to up to 4 logically linked single-point indications. The single-point indications can be
inverted.
Rule for Linking Indications to a Group Indication
In a group indication, up to 4 indications can sequentially be linked logically. The indications 1 to 4 are always
linked successively as follows:
Indication 1 with Indication 2 = Indication 1/2
Indication 1/2 with Indication 3 = Indication 1/2/3
Indication 1/2/3 with Indication 4 = Group indication
[sc_q200_regular_4x_1, 1, en_US]
[dw_q200_regular_4x_1, 1, en_US]
Figure 2-174
[sc_q200_regular_2x_1, 1, en_US]
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020
Default Setting
0.00
1.0 %
ON
Example: Linking 4 Indications to a Group Indication
2.10 Other Device Functions
Setting Range
-1 000 000 000.00 to +1 000 000 000.00 (unit)
0.0 % to 10.0 %
ON
OFF (O)
Acc. to the current configuration
Device Functions
227