Ground-Fault Parameter Active Group Setting; Fault Indication - Siemens SICAM Manual

Feeder condition monitor
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

Table 4-7
Parameter
I>
Table 4-8
Parameter
Operate time
Time multiplier setting (k)
NOTE
i
i
The IDMT function is not applicable for the ground fault I
If tI> is set to zero, the NI trip time curve according to the IEC characteristics is calculated based on the
following formula.
I
is the fault current. I
fault
The fixed value of k is 0.09.
NOTE
i
i
For setting the IDMT characteristics curves, set tI> = 0.

Ground-Fault Parameter Active Group Setting

4.1.6
The device provides 2 groups of settings (Group 1 and Group 2) for the Neutral-point treatment param-
eter (solid, resonant, isolated) and Ground-fault parameters (I
You can select the active group and its group parameter from HMI and Modbus, by holding register (address
42) or by turning ON the coil 12. When the device is indicating a fault, you cannot change the active group
and its parameters.
At any time, only one selected group of settings is active. These parameters are used for detecting the ground
fault.
For more information about the active-group switching coil, refer to
For more information about the active group, refer to

Fault Indication

4.1.7
When the device detects a fault, the following components are activated:
LED
The red LED is turned on and indicates a fault.
LCD
The LCD displays fault current values with the fault type.
Modbus
The device sends the fault current, fault type, and additional fault information to the RTU.
If a fault is detected, the red LED flashes every 1 s if the device is not powered through an auxiliary supply.
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Operate Level
Attribute
Operate level
Operate Time
Attribute
char = IEC-NI
0.09
is the setting value of the pickup current.
set
Value
110 % of I> ±5 %
Value
±5 % absolute or ±40 ms
.
N
>, tI
>, V
>, tV
N
N
NG
Table
B-10.
Active Group, Page
121.
Device Functions
4.1 Description
>, and I
).
NG
dir
37

Hide quick links:

Advertisement

Table of Contents
loading