Communication
Notes:
•
The communication protocol is automatically detected by the AiRanger DPL
Plus and shown via LED on the motherboard.
•
Ground shield at one end only.
Serial
RS-232
to customer device,
RS-232 port
15m (50ft) max
SmartLinx
Refer to the appropriate SmartLinx manual for installation and wiring.
Level System Synchronization
Avoid mounting the AiRanger DPL Plus near another ultrasonic level monitor. Likewise,
when more than one monitor is installed within a single plant/facility, ensure the
transducer cables of each system are run in separate grounded metal conduits. If this
system separation is impractical, or if measurement difficulties are encountered, system
synchronization may be required.
Synchronize the AiRanger DPL Plus with another AiRanger DPL Plus
1.
Mount the level monitors together in one cabinet.
2.
Ensure the level monitors share a common power (mains) supply, and ground
(earth).
3.
Interconnect the SYNC terminals of the level monitors to be synchronized.
Note:
To synchronize the AiRanger DPL Plus with other Siemens Milltronics
ultrasonic level monitors, contact Siemens Milltronics or your local distributor.
Page 16
AiRanger DPL Plus – INSTRUCTION MANUAL
RS-485
to customer device,
RS-485 port
1200 (4,000 ft) max