9810 series - User manual
A/C mode
If you set Input Mode to A/C, the digital input port is configured to detect the presence of a low
voltage AC signal. The next illustration shows how a digital input can be used to monitor the
operation of a low voltage AC fan controller.

IRIG-B time synchronization

You can use a digital input to synchronize the meter time to an IRIG-B time source.
You can connect an IRIG-B time source to one of meter's digital inputs for IRIG-B time
synchronization. For IRIG-B time synchronization, you must configure both the meter's digital
input and the meter's clock.
NOTE: For improved accuracy use the digital inputs on the meter base.

Configuring onboard digital inputs using ION Setup

You can use ION Setup to configure your meter's digital inputs.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Onboard I/O > Digital Inputs. The tabs correspond to each digital input. Click on the
tab for the digital input you want to edit.
4. Configure the digital input by selecting the parameter and clicking Edit.
5. After the parameter is configured, click OK to save the setting to the meter.
7EN05-0390-08
Inputs/Outputs
136