2.7
SICAM EFI Terminal Details
The following figure shows the terminal blocks along with device sectional view of SICAM EFI.
[dw̲efiterminaldiagram, 1, en̲US]
Figure 2-5
Table 2-2
Termin
Pin No.
al Block
X1
1, 2
E
3
X2
4
5
X3
6 (+)
7 (‒)
X4
8, 9
X5
10 (C)
11 (NO)
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022
SICAM EFI Terminal Details
Terminal Specifications along with Recommended Cable and Lug Specifications
Description
Auxiliary supply input (AC)
Terminal connector for functional ground. This
needs to be connected irrespective of whether
the device is powered using AC/DC supply or
battery.
Sensor input terminal 1 (S1)
Sensor input terminal 2 (S2)
Auxiliary supply input (DC)
Remote reset/Low voltage reset (LVR) input
Remote function check (self-test) input.
During fault occurrence, this terminal operates
as remote reset input. During no fault condition,
this terminal operates as remote function check
input.
Signal lamp output
2.7 SICAM EFI Terminal Details
Cable Cross-
Lug (Tubular
section
Terminal)
1.5/2.5 mm
1.5/2.5 mm
2
0.5 mm
0.5 mm
2
1.5/2.5 mm
1.5/2.5 mm
2
0.5 mm
0.5 mm
2