CHAPTER 3 PRIMEPOWER850 Rack-mount Type (16U) Server
Table 3.5 Installation specifications of the PRIMEPOWER850 rack-mount type
(16U) server (2/3)
Item
Temperature Operating
(Note 3)
Not operating
Humidity
Operating
Not operating
Heat
1 SB (8CPU)
dissipation
2 SB (16CPU) 13,860 kJ/hr (13,136 BTU/hr)
Vibration
Operating
Not operating
Noise level (Note 4)
Installation type
Note 2: In model names, x is any letter from A to Z. And y is any letter from A to Z
or any digit from 0 to 9.
Note 3: A warning message appears during operation if the ambient temperature
exceeds 35 °C (95°F). Take immediate corrective action.
Note 4: The indicated noise level is the mean value of noise measured when the
main unit is installed in an 1800-mm rack in a low-noise anechoic chamber.
The actual noise level measured at the installation site may be greater than
the indicated value because of background noise and echoes.
Note 5: Fujitsu Siemens Computers does not use the maintenance tray, so that the
rack mount server only needs 16 (instead of 17) height units).
72
(Model name: PW0VCRyyyx,
PW0VDRyyyx, PW0VFRyyyx,
PW0VGRyyyx) (Note 2)
5 - 35 °C ( +41 ~ +95 °F)
[When installed at height of 0 to 1500 m (0 to 4921.2 ft) above sea level]
5 - 33 °C ( +41 ~ +91.4 °F)
[When installed at height of 1500 to 2000 m (4921.2 to 6561.6 ft) above
sea level]
5 - 32 °C ( +41 ~ +89.6 °F)
[When installed at height of 2000 to 2500 m (6561.6 to 8202 ft) above
sea level]
5 - 30 °C ( +41 ~ +86 °F)
[When installed at height of 2500 to 3000 m (8202 to 9842.4 ft) above
sea level]
0 - 50 °C ( +32 ~ +122 °F)
20 ~ 80 % RH (Non-Condensing)
8 ~ 80 % RH (Non-Condensing)
8,460 kJ/hr (8,018 BTU/hr)
0.2 G
0.4 G
60 dBA
Rack-mount (16 pitch) (Note 5)
Specifications
(Model name: PW0V0CR1x,
PW0V0CR6x, PW0V0DR1x,
PW0V0DR6x, PW0V0AR2x,
PW0V0AR7x)
6,480 kJ/hr (6,142 BTU/hr)
11,340 kJ/hr (10,748 BTU/hr)
50 dBA
U41261-J-Z816-4-76