l Install the PRIMEPOWER850 rack-mount type (16U) server away from EM noise
generating devices such as photocopiers, air conditioners, or welders.
l Take electrostatic prevention measures. Note that many carpets generate static
electricity that can cause the PRIMEPOWER850 rack-mount type (16U) server to
malfunction.
l When moving the PRIMEPOWER850 rack-mount type (16U) server, do not pull
on the front cover. This could cause damage to the unit.
3.3.2

Installation specifications

Table 3.5
type (16U) server.
Table 3.5 Installation specifications of the PRIMEPOWER850 rack-mount type
(16U) server (1/3)
Item
Weight (Note 1)
Power
Input voltage
supply
Input frequency 50/60 Hz (+2 / -4 %)
Input Power 1 SB (8CPU)
2 SB (16CPU) 3900 VA
Maximum
1 SB (8CPU)
current
2 SB (16CPU) 19.5 A
consumption
Leakage current
Ground resistance
Note 1: Not including the rack-mount rails and the maintenance tray
Note 2: In model names, x is any letter from A to Z. And y is any letter from A to Z
or any digit from 0 to 9.
U41261-J-Z816-4-76
lists the installation specifications of the PRIMEPOWER850 rack-mount
(Model name: PW0VCRyyyx,
PW0VDRyyyx, PW0VFRyyyx,
PW0VGRyyyx) (Note 2)
160 kg (352.8 lb.) (maximum )
Single phase, 200 to 240 VAC (+10%)
2400 VA
12.0 A
Less than 5.0 mA (per cable)
Less than 100 Ω
3.3 Preparations for Operation
Specifications
(Model name: PW0V0CR1x,
PW0V0CR6x, PW0V0DR1x,
PW0V0DR6x, PW0V0AR2x,
PW0V0AR7x)
2000 VA
3500 VA
10.0 A
17.5 A
71