Message Format In Rtu Mode - Delta Electronics DVP15MC11T Operation Manual

Table of Contents

Advertisement

A.2

Message Format in RTU Mode

Communication data structure
Start
Communication address
Function code
Data (n-1)
.......
Data 0
Low byte of CRC check
High byte of CRC check
End
Communication address
The range of a valid communication address is 0~254. The communication address 0 indicates
to broadcast the message to all slaves and the slaves which have received the broadcast
message do not make any response. If the communication address is not 0, slaves will reply to
master as normal. For example, to communication with the slave with the communication
address of 16, the address of the slave is set as 0x10 since decimal 16 is equal to hexadecimal
10.
Function code and data
The data format is determined by function codes.
For example, to read the data of two continuous addresses with 0x0000 as start address in
DVP15MC11T, the address of DVP15MC11T is 1, 0x0000 is the Modbus address of %MW0 in
DVP15MC11T PLC.
The data in the communication cable and the explanation on them are shown below:
PC→DVP15MC11T: "01 03 00 00 00 02 C4 0B"
DVP15MC11T→PC: "01 03 04 00 01 02 00 2A 32"
Request message:
Start
Communication address
Function code
High byte of Modbus address
Low byte of Modbus address
Read high byte of data number
Read low byte of data number
Low byte of CRC check sum
High byte of CRC check sum
End
No input data for more than 10ms
Slave address: 8-bit binary address
Function code: 8-bit binary address
Data content
n × 8 bit binary data, n<=202
CRC check sum
CRC check sum is composed of two 8-bit binary data
Field name
Appendix A. Modbus Communication
Character
No input data for more than 10ms
01
03
00
00
00
02
C4
0B
No input data for more than 10ms
A_
A-5