Delta Electronics DVP15MC11T Operation Manual page 277

Table of Contents

Advertisement

DVP15MC11T Operation Manual
8.15.2
TO
FB/FC
The TO instruction writes data to the specified CR registers of the left-side
FB
module and right-side module.
Input Parameters
Parameter name
StationID
Execute
CR
Num
_8
DesPtr
Output Parameters
Parameter name
Done
Busy
Active
Error
ErrorID
8-206
Explanation
St ationID
Execute
CR
Nu m
De sPt r
Function
The position of the
extension module
connected to the left side
or right side of
DVP15MC11T
The instruction is executed
when Execute changes
from FALSE to TRUE.
The number of the first CR
(Controlled Register) to be
read
Number of CR registers
which are to be read
The CR value written by
the instruction
Function
TRUE when the instruction execution is completed.
TRUE when the instruction is being executed.
TRUE when the instruction is being executed.
TRUE while there is an error.
Contains the error code when an error occurs. Please
refer to section 12.2 for the corresponding error ID.
TO instance
_
TO
Done
Busy
Active
Error
ErrorID
Valid range
Data type
(Default)
Position range of
left-side module:
100~107
Position range of
right-side special
module: 0~7
The position of the first
USINT
module at the left side of
DVP15MC11T is 100
and the position of the
first module at the right
side of DVP15MC11T is
0.
(The variable value
must be set)
TRUE or FALSE
BOOL
(FALSE)
0~ max. CR number
UINT
(The variable value
must be set)
1~64
USINT
(The variable value
must be set)
The range of the data
type of the written CR
INT or
value
DINT
(The variable value
must be set)
Applicable model
DVP15MC11T
Validation timing
When Execute
changes from
FALSE to TRUE
When Execute
changes from
FALSE to TRUE
When Execute
changes from
FALSE to TRUE
When Execute
changes from
FALSE to TRUE
Data type
Valid range
BOOL
TRUE / FALSE
BOOL
TRUE / FALSE
BOOL
TRUE / FALSE
BOOL
TRUE / FALSE
WORD
-