Delta Electronics Programmable Logic Controller DVP04AD-H2 Instruction Sheet

Delta Electronics Programmable Logic Controller DVP04AD-H2 Instruction Sheet

Programmable logic controller

Advertisement

Quick Links

Warning
Please read this instruction carefully before use.
Switch off the power before wiring.
DVP04AD-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device
(e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may occur.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all
the wiring again before switching on the power.
DO NOT touch any terminal when the power is switched on. DO NOT touch any internal circuit in 1 minute after the
power is switched off.
Make sure the groud terminal
is correctly grounded in order to prevent electromagnetic interference.
Introduction
Model Explanation and Peripherals
■ ■ ■ ■
Thank you for choosing Delta DVP series PLC. DVP04AD-H2 is able to receive 4 points of analog input
signals (voltage or current) and convert them into 14-bit digital signals. Besides, through FROM/TO
instructions in DVP-EH2 MPU program, the data in DVP04AD-H2 can be read or written. There are 49
16-bit control registers (CR) in DVP04AD-H2.
You can select voltage or current output by wiring. Range of voltage output: ± 1 0V DC (resolution:
1.25mV). Range of current output: ± 2 0mA (resolution: 5µA).
Product Profile (Indicators, Terminal Block, I/O Terminals)
■ ■ ■ ■
Unit: mm
1
DIN rail (35mm)
6
Terminals
2
Connection port for extension modules
7
Mounting hole
Model name
I/O terminals
3
8
4
POWER, ERROR, A/D indicator
9
Mounting port for extension modules
DIN rail clip
5
External Wiring
■ ■ ■ ■
Voltageinput
-10V~+10V
CH1
100K
V+
250
*5
I+
COM
FG
Shielding cable*1
AG
Current input
CH4
100K
-20mA~+20mA
V+
*2
250
I+
COM
FG
Shielding cable*1
AG
*3
Terminal of
power module
DC/DC
24+
*4
24-
Converter
Systemgrounding
Earth
(100 or less)
*1. When performing analog input, please isolate other power wirings.
*2. If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the wiring to 0.1
~ 0.47µF 25V capacitor.
*3. Please connect the
terminal on both the power modules and DVP04AD-H2 to the system earth point and ground the system
contact or connect it to the cover of power distribution cabinet.
.
Note: DO NOT wire empty terminals
Specifications
Analog/Digital (4A/D) module
Voltage input
Power supply voltage
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
Analog input channel
4 channels/module
Range of analog input
±10V
±20mA
Range of digital conversion
±8,000
±4,000
Resolution
14 bits (1
= 2.5mV)
13 bits (1
LSB
Input impedance
0.5 or lower
±0.5% when in full scale (25°C, 77°F)
Overall accuracy
±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
Responding time
3ms × the number of channels
Internal circuit and analog output terminals are isolated by optical coupler.
Isolation
No isolation among analog channels.
Range of absolute input
±15V
±32mA
Digital data format
13 significant bits out of 16 bits are available; in 2's complement
Average function
Yes. Available for setting up in CR#2 ~ CR#5; range: K1 ~ K20.
Self-diagnosis
Upper and lower bound detection/channel
ASCII/RTU mode. Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200
Communication mode
bps. ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even
(RS-485)
bit, 1 stop bit (8, E, 1). RS-485 cannot be used when connected to PLC MPU.
The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is
When connected to DVP-PLC
the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect
MPU in series
to MPU and will not occupy any digital I/O points.
Other Specifications
■ ■ ■ ■
ENGLISH
Power supply
Max. rated power consumption 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2.5W, supplied by external power.
Environment
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2
Operation/storage
Storage: -25°C ~ 70°C (temperature); 5 ~ 95% (humidity)
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
Vibration/shock immunity
(TEST Ea)
Control Registers
RS-485
CR
Latched
Register content
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
parameter
#
address
Set up by the system. DVP04AD-H2 model code = H'6400.
#0
H'4000
R
Model name
The user can read the model name from the program and see if
the extension module exists.
Reserved
CH4
Input mode: Default = H'0000
Mode 0: Voltage input (-10V ~ +10V)
#1
H'4001
R/W
Input mode setting
Mode 1: Voltage input (-6V ~ +10V)
Mode 2: Current input (-12mA ~ +20mA)
Mode 3: Current input (-20mA ~ +20mA)
CR#1: The working mode of the two channels in the analog output module. There are 4 modes for each channel which
can be set up separately. For example, if the user needs to set up CH1: mode 2 (b2 ~ b0 = 010) and CH2: mode 1 (b5 ~
b3 = 001), CR#1 has to be set as H000A and the higher bits (b12 ~ b15) have to be reserved. Default value = H'0000.
#2
H'4002
R/W
CH1 average time
Range of settings in CH1 ~ CH4: K1 ~ K20. Default = K10.
#3
H'4003
R/W
CH2 average time
Please note that the average time settings at CR#2 ~ CR#5 only
#4
H'4004
R/W
CH3 average time
need to be written in once.
#5
H'4005
R/W
CH4 average time
#6
H'4006
R
CH1 input average
#7
H'4007
R
CH2 input average
Average of input signals at CH1 ~ CH4
#8
H'4008
R
CH3 input average
#9
H'4009
R
CH4 input average
CR#6 ~ CR#9: The average of the signals at CH1~CH4 obtained from the settings in CR#2~CR#5. For example, if the
settings in CR#2~CR#5 is 10, the content in CR#6~CR#9 will be the average of the most recent 10 signals at CH1~CH4.
#12
H'400C
R
CH1 input present value
8
#13
H'400D
R
CH2 input present value
Present value of input signals at CH1 ~ CH4
#14
H'400E
R
CH3 input present value
#15
H'400F
R
CH4 input present value
Adjusted OFFSET value of
#18
H'4012
R/W
CH1
Adjusted OFFSET value of
OFFSET settings at CH1 ~ CH4.
#19
H'4013
R/W
CH2
Default = K0; Unit: LSB.
When voltage input, range: K-4,000 ~ K4,000
Adjusted OFFSET value of
#20
H'4014
R/W
CH3
When current input, range: K-4,000 ~ K4,000
Adjusted OFFSET value of
#21
H'4015
R/W
CH4
RS-485
CR
Latched
Register content
parameter
#
address
CH1
#24
H'4018
R/W
Adjusted GAIN value of CH1
100K
#25
H'4019
R/W
Adjusted GAIN value of CH2
#26
H'401A
R/W
Adjusted GAIN value of CH3
#27
H'401B
R/W
Adjusted GAIN value of CH4
CH4
CR#24 ~ CR#27: The adjusted GAIN value of CH1 ~ CH4, representing the analog input voltage or current when the
100K
analog signal is converted into digital value 4,000.
Note: GAIN value – OFFSET value = +800
~ +12,000
LSB
When GAIN – OFFSET is small (steep oblique), the resolution of input signal will be finer and variation on the digital value
will be greater. When GAIN – OFFSET is big (gradual oblique), the resolution of input signal will be rougher and variation
+15V
on the digital value will be smaller.
AG
-15V
#30
H'401E
R
Error status
CR#30: Error status value (see the table below)
Error status
Content
Abnormal power supply
K1 (H'1)
Incorrect mode setting
K4 (H'4)
OFFSET/GAIN error
K8 (H'8)
Hardware malfunction
K16 (H'10)
Abnormal digital range
K32 (H'20)
Incorrect average times setting
K64 (H'40)
Instruction error
K128 (H'80)
Current input
Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the
same time. 0 = normal; 1 = error.
Communication address
#31
H'401F
R/W
setting
= 5µA)
LSB
Communication speed (baud
#32
H'4020
R/W
rate) setting
Returning to default setting;
#33 H'4021
R/W
OFFSET/GAIN tuning
authorization
CR#33: For authorizations on some internal functions, e.g. OFFSET/GAIN tuning. The latched function will store the
output setting in the internal memory before the power is cut off.
#34
H'4022
R
Firmware version
#35 ~ #48
Symbols:
: Latched (when written in through RS-485 communication);
: Non-latched;
R: Able to read data by FROM instruction or RS-485 communication;
W: Able to write data by TO instruction or RS-485 communication.
LSB (Least Significant Bit):
For voltage input: 1
= 10V/8,000 = 1.25mV.
LSB
CR#0 ~ CR#34: The corresponding parameter addresses H'4032 ~ H'4022 are for users to read/write data by
RS-485 communication. When using RS-485, the user has to separate the module with MPU first.
a. Communication baud rate: 4,800/9,600/19,200/38,400/57,600/115,200 bps.
b. Modbus ASCII/RTU communication protocols: ASCII data format (7-bit, even bit, 1 stop bit (7, E, 1)); RTU
data format (8-bit, even bit, 1 stop bit (8, E, 1)).
c. Function: H'03 (read register data); H'06 (write 1 word datum to register); H'10 (write many word data to
CH3
CH2
CH1
register).
d. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written
by MPU through TO/DTO instruction.
Adjusting A/D Conversion Curve
Voltage input mode:
CR#1 mode 0
+8,000
Mode0
CR#1 mode 1
+4,000
Mode1
0
5V
6 V
GAIN
-10V
-6V
2V
10V
O F FS E T
G AIN
-4,000
OFFSET
Voltage input
-8,000
GAIN - OFFSET
Current input mode:
CR#1 mode 2
Mode3
+4,000
Mode2
CR#1 mode 3
-20 A
-12mA
0
GAIN
4mA
20mA
OF F SE T
GAIN
OFFSET
Current input
-4,000
GAIN - OFFSET
The user can adjust the OFFSET/GAIN curves according to the actual needs by changing the OFFSET value
(CR#18 ~ CR#21) and GAIN value (CR#24 ~ CR#27).
注 意 事 項
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
GAIN settings at CH1 ~ CH4.
Default = K4,000; Unit: LSB.
(OPEN TYPE)
When voltage input, range: K-3,200 ~ K16,000
When current input, range: K-3,200 ~ K10,400
(voltage) or +800
~ +6,400
(current).
LSB
LSB
LSB
產 品 簡 介
Register for storing all error status.
See the table of error status for more information.
說 明 及 週 邊 裝 置
b15 ~ b8
b7
b6
b5
b4
b3
b2
b1
b0
0
0
0
0
0
0
0
1
0
0
0
0
0
1
0
0
0
0
0
0
1
0
0
0
Reserved
0
0
0
1
0
0
0
0
±20mA
0
0
1
0
0
0
0
0
0
1
0
0
0
0
0
0
產 品 外 觀 及 各 部 介 紹
1
0
0
0
0
0
0
0
For setting RS-485 communication address.
Range: 01 ~ 254. Default = K1.
For setting up communication speed: 4,800/9,600/19,200/
38,400/57,600/115,200 bps. ASCII data format: 7-bit, even bit, 1
stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1 stop bit (8,
E, 1). Default = H'0002.
b0: 4,800 bps. b1: 9,600 bps (Default).
b2: 19,200 bps. b3: 38,400 bps.
b4: 57,600 bps. b5: 115,200 bps
b6 ~ b13: Reserved.
b14: High/low bit exchange of CRC checksum (only valid in
RTU mode).
b15: Switch between ASCII/RTU mode; 0 = ASCII mode
(Default).
Reserved
CH4
CH3
CH2
CH1
1
DIN
(35mm)
Default = H'0000. Take the setting of CH1 for example:
2
/
1. When b0 = 0, the user is allowed to tune CR#18 (OFFSET)
3
and CR#24 (GAIN) of CH1. When b0 = 1, the user is not
4
allowed to tune CR#18 and CR#24 of CH1.
2. b1 represents whether the OFFSET/GAIN tuning registers
5
DIN
are latched. b1 = 0 (default, latched); b1 = 1 (non-latched)
3. When b2 = 1, all settings will return to default values.
外 部 配 線
Displaying the current firmware version In hex; e.g. version 1.0A
is indicated as H'010A.
For system use
For current input: 1
= 20mA/4,000 = 5µA.
LSB
*1
*2
*3
規 格
/
(4A/D)
GAIN = 5V (4,000
). OFFSET = 0V (0
).
LSB
LSB
GAIN = 6V (4,800
). OFFSET = 2V (1,600
).
LSB
LSB
The voltage input value when the digital output value =
K4,000.
Range: -3,200
~ +16,000
.
LSB
LSB
The voltage output value when the digital input value = K0.
Range: -4,000
~ +4,000
.
LSB
LSB
Range: +800
~ +12,000
.
LSB
LSB
GAIN = 12mA (2,400
). OFFSET = 4mA (800
).
LSB
LSB
GAIN = 10mA (2,000
). OFFSET = 0mA (0
).
LSB
LSB
The current input value when the digital output value =
K2,000.
Range: -3,200
~ +10,400
.
LSB
LSB
The current input value when the digital output value = K0.
Range: -4,000
~ +4,000
.
LSB
LSB
(RS-485)
Range: +800
~ +6,400
.
LSB
LSB
DVP-PLC
/
DVP
DVP04AD-H2
4
14
DVP-EH2
FROM/TO
49
CR (Control Register)
16 bits
±10V DC
1.25mV
5µA
8
mm
6
7
8
9
/
電 壓 輸 入
-10V~+10V
CH1
100K
V+
CH1
250
*5
I+
100K
COM
隔 離 線
* 1
FG
AG
電 流 輸 入
CH4
100K
-20mA~+20mA
V+
CH4
*2
250
I+
100K
COM
FG
隔 離 線
* 1
AG
*3
接 至 電 源 模
組 之 端
+15 V
DC/DC
24+
*4
AG
轉 換 器
24-
系 統 接 地 點
-15V
接 地
(
接 地 阻 抗
100
以 下
)
0.1 ~ 0.47µF 25V
DVP04AD-H2
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
4
/
±10V
±20mA
±8,000
±4,000
14 bits (1
= 2.5mV)
13 bits (1
= 5µA)
LSB
LSB
200K
250
±0.5%
(25°C, 77°F)
±1%
(0 ~ 55°C, 32 ~ 131°F)
3ms ×
±15V
±32mA
16
13 bits
CR#2 ~ CR#5
K1 ~ K20
/
ASCII/RTU
(4,800/9,600/19,200/38,400/57,600/115,200 bps) ASCII
7-bit
1 stop bit (7, E, 1) RTU
8-bit
1 stop bit (8, E, 1)
PLC
RS-485
0
7
8
I/O