Delta Electronics DVP15MC11T Operation Manual page 566

Table of Contents

Advertisement

PDO
SDO
SYNC
Time Stamp
EMCY
Boot-up
NMT
The format of the control message for the node state:
COB-ID
0
The command specifiers are listed below.
Command specifier (hex)
01
02
80
81
82
Error Control services
The error control service is used to detect the disconnection of the node in the network. The error
control services can be classified into two types, Heartbeat and Node Guarding. The PLC only
supports Heartbeat. For example, the master can detect the disconnection of the slave only after the
slave enables the Heartbeat service.
The Heartbeat principle is illustrated as follows. The Heartbeat producer transmits the Heartbeat
message according to the Heartbeat producing time which is set. One or more Heartbeat consumers
detect the message transmitted by the Heartbeat producer. If the consumer does not receive the
message transmitted by the producer within the timeout period, the heartbeat event generated
indicates that the CANopen communication is abnormal.
Initialization Pre-operational Operational
X
X
X
X
X
X
Byte 0
Command specifier (CS)
Start the remote node
Stop the remote node
Enter the pre-operational state
Reset the application layer
Reset the communication
Appendix C CANopen Protocol
Stopped
X
X
X
X
X
X
Byte 1
Slave address
(0: Broadcast)
Function
X
C_
C-5