Measurement Ranges Of The Analog Outputs For Voltage And Current (Sb And Em) - Siemens SIMATIC S7 System Manual

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

Technical specifications
A.4 Analog inputs and outputs expansion modules (EMs)
Table A- 113 Analog input representation for current (SB and EM)
System
Decimal
Hexadecimal
32767
7FFF
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-4864
ED00
-4865
ECFF
-32768
8000
A.4.7

Measurement ranges of the analog outputs for voltage and current (SB and EM)

Table A- 114 Analog output representation for voltage (SB and EM)
System
Decimal
Hexadecimal
32767
7FFF
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
AF00
-27648
9400
-27649
93FF
-32512
8100
-32513
80FF
-32768
8000
In an overflow or underflow condition, analog outputs will take on the substitute value of the STOP mode.
1
750
0 mA to 20 mA
23.70 mA
23.52 mA
20 mA
15 mA
723.4 nA
0 mA
-3.52 mA
± 10 V
See note 1
See note 1
11.76 V
10 V
7.5 V
361.7 μ V
0 V
-361.7 μ V
-7.5 V
-10 V
-11.76 V
See note 1
See note 1
Current measuring range
4 mA to 20 mA
22.96 mA
22.81 mA
20 mA
16 mA
4 mA + 578.7 nA
4 mA
1.185 mA
Voltage Output Range
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
System Manual, V2.3, 07/2017, A5E03822230-AF
Overflow
Overshoot range
Nominal range
Undershoot range
Underflow
S7-200 SMART

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-200 smart

Table of Contents