Siemens SIMATIC S7 System Manual page 292

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

Program instructions
7.7 Pulse output
Table 7- 17
Q0.0
SM66.4
SM66.5
SM66.6
SM66.7
Q0.0
SM67.0
SM67.1
SM67.2
SM67.3
SM67.4
SM67.5
SM67.6
SM67.7
Q0.0
SMW68
292
SM locations for the PTO/PWM control registers
Q0.1
Q0.3
SM76.4
SM566.4
PTO delta calculation error (due to an add error):
SM76.5
SM566.5
PTO profile disabled (due to user command):
SM76.6
SM566.6
PTO/PWM pipeline overflow/underflow:
SM76.7
SM566.7
PTO idle:
Q0.1
Q0.3
SM77.0
SM567.0
PTO/PWM update the frequency/cycle time:
SM77.1
SM567.1
PWM update the pulse width time:
SM77.2
SM567.2
PTO update the pulse count value:
SM77.3
SM567.3
PWM time base:
SM77.4
SM567.4
Reserved
SM77.5
SM567.5
PTO single/multiple segment operation:
SM77.6
SM567.6
PTO/PWM mode select:
SM77.7
SM567.7
PWM enable:
Q0.1
Q0.3
SMW78
SMW568 PTO frequency or PWM cycle time value: 1 to 65,535 Hz (PTO); 2
to 65,535 (PWM)
Status bits
0 = No error
1 = Aborted due to error
0 = Profile not manually disabled
1 = User disabled profile
0 = No overflow/underflow
1 = Overflow/underflow
0 = In progress
1 = PTO idle
Control bits
0 = No update
1 = Update frequency/cycle time
0 = No update
1 = Update pulse width
0 = No update
1 = Update pulse count
0 = 1 µs/tick
1 = 1 ms/tick
0 = Single
1 = Multiple
0 = PWM
1 = PTO
0 = Disable
1 = Enable
Other registers
System Manual, V2.3, 07/2017, A5E03822230-AF
S7-200 SMART

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-200 smart

Table of Contents