Analog modules
5.4 Representation of analog values
5.4.4

Representation of analog values in voltage measuring ranges

Table 5-9
Representation of analog values in the ±1 V to ±10 V voltage measuring ranges
System
Dec.
118,515 % 32767
117,593 % 32512
117,589 % 32511
27649
100,000 % 27648
75,000 % 20736
0,003617 % 1
0 % 0
- 1
- 75,00 % - 20736
- 100,000 % - 27648
- 27649
- 117,593 % - 32512
- 117,596 % - 32513
- 118,519 % - 32768
Table 5-10
Representation of analog values in the ±25 to ±500 mV voltage measuring ranges
System
Dec.
118,515 % 32767
117,593 % 32512
117,589 % 32511
27649
100,000 % 27648
75 % 20736
0,003617% 1
0 % 0
- 1
- 75,00 % - 20736
- 100,000% - 27648
- 27649
- 117,593% - 32512
- 117,596% - 32513
- 118,519% - 32768
172
Hex.
± 10 V
7FFF
11.851 V
7F00
7EFF
11.759 V
6C01
6C00
10 V
5100
7.5 V
1
361.7 µV
0
0 V
FFFF
AF00
- 7.5 V
9400
- 10 V
93FF
8100
- 11.759 V
80FF
8000
- 11.851 V
Hex.
± 500 mV
± 250 mV
7FFF
592.6 mV
296.3 mV
7F00
7EFF
587.9 mV
294.0 mV
6C01
6C00
500 mV
250 mV
5100
375 mV
187.54 mV
1
18.08 µV
9.04 µV
0
0 mV
0 mV
FFFF
AF00
- 375 mV
-187.54 mV
9400
- 500 mV
- 250 mV
93FF
8100
- 587.9 mV
- 294.0 mV
80FF
8000
- 592.6mV
- 296.3 mV
Voltage measuring range
± 5 V
± 2.5 V
5.926 V
2.963 V
5.879 V
2.940 V
5 V
2.5 V
3.75 V
1.875 V
180.8 µV
90.4 µV
0 V
0 V
- 3.75 V
- 1.875 V
- 5 V
- 2.5 V
- 5.879 V
- 2.940 V
- 5.926 V
- 2.963 V
Voltage measuring range
± 80 mV
94.8 mV
59.3 mV
94.1 mV
58.8 mV
80 mV
50 mV
60 mV
37.5 mV
2.89 µV
1.81 µV
0 mV
0 mV
- 60 mV
- 37.5 mV
- 80 mV
- 50 mV
- 94.1 mV
- 58.8 mV
- 94.8mV
- 59.3 mV
Reference Manual, Ausgabe 11/2016, A5E00850736-08
± 1 V
1.185 V
Overflow
1.176 V
Overshoot range
1 V
0.75 V
36.17 µV
Nominal range
0 V
- 0.75 V
- 1 V
Undershoot range
- 1.176 V
Underflow
- 1.185 V
± 50 mV
± 25 mV
29.6 mV
29.4 mV
25 mV
18.75 mV
904.2 nV
0 mV
- 18.75 mV
- 25 mV
- 29.4 mV
- 29.6 mV
S7-400 Automation System Module Data
Overflow
Overshoot
range
Nominal range
Undershoot
range
Underflow

Hide quick links: