Siemens SIMATIC S7 System Manual page 310

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

Program instructions
7.9 PID
Screen
310
Description
You enter the loop output options:
How the loop output is to be
scaled:
Analog
Digital
Analog scaling parameter:
Unipolar (default: 0 to 27648;
can edit)
Bipolar (default: -27648 to
24678; can edit)
Unipolar 20% offset (range:
5530 to 27648; is set and un-
changeable
Analog range parameter: Assign
the loop output range. The possible
range is -27648 to +27648, de-
pending on your scaling selection.
You can assign what conditions to
recognize with alarm inputs. Use the
checkboxes to enable the alarms as
required:
Low Alarm (PV): Set normalized
low alarm limit from 0.0 to high
alarm limit; default is 0.10.
High Alarm (PV): Set normalized
high alarm limit from low alarm limit
to 1.00; default is 0.90.
Analog Input Error: Assign where
the input module is attached to the
PLC.
System Manual, V2.3, 07/2017, A5E03822230-AF
S7-200 SMART