Siemens SIMATIC S7 System Manual page 818

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

Special memory (SM) and system symbol names
D.15 SMB66-SMB85 (PTO0/PWM0, PTO1/PWM1), SMB166-SMB169 (PTO0), SMB176-SMB179 (PTO1), and
SMB566-SMB579 (PTO2/PWM2): high-speed outputs
Table D- 17
High-speed output 2 configuration and control
S7-200 SMART
symbol name
PTO2_Status
PLS2_Abort_AE
PLS2_Disable_UC
PLS2_Ovr
PLS2_Idle
PLS2_Ctrl
PLS2_Cycle_Update
PWM2_PW_Update
PTO2_PC_Update
PLS2_TimeBase
PTO2_Operation
PLS2_Select
PLS2_Enable
PLS2_Cycle
PWM2_PW
PTO2_PC
PTO2_Seg_Num
PTO2_Profile_Offset
818
SM address
Description
SMB566
PTO2 Status
SM566.4
PTO2 profile was aborted due to an add error: FALSE: No abort;
TRUE:Aborted
SM566.5
PTO2 user manually disabled a PTO profile while it was running: FALSE:
Not disabled; TRUE: Manually disabled
SM566.6
PTO2 pipeline overflow/underflow, loading pipeline while full or transfer-
ring an empty pipeline: FALSE: No overflow; TRUE: Pipeline over-
flow/underflow
SM566.7
PTO2 idle: FALSE: PTO in progress; TRUE: PTO is idle
SMB567
Monitor and control PTO2 (Pulse Train Output) and PWM2 (Pulse Width
Modulation) for Q0.3
SM567.0
PTO2/PWM2 update the cycle time or frequency value: FALSE: No up-
date; TRUE: Write new cycle time/frequency
SM567.1
PWM2 update the pulse width value: FALSE: No update; TRUE: Write
new pulse width
SM567.2
PTO2 update the pulse count value: FALSE: No update; TRUE: Write
new pulse count
SM567.3
PWM2 time base: FALSE: 1 μs/tick, TRUE: 1 ms/tick
SM567.4
Reserved
SM567.5
PTO2 select single/multiple segment operation: FALSE: Single; TRUE:
Multiple
SM567.6
PTO2/PWM2 mode select: FALSE: PWM; TRUE: PTO
SM567.7
PTO2/PWM2 enable: FALSE: disable; TRUE: enable
SMW568
Word data type: PWM2 cycle time value (2 to 65,535 units of time base);
PTO2 frequency value (1 to 65,535 Hz)
SMW570
Word data type: PWM2 pulse width value (0 to 65,535 units of time base)
SMD572
Double Word data type: PTO2 pulse count value (1 to 2,147,483,647)
SMB576
Byte data type: The currently executing segment number for PTO2's
profile
SMW578
Word data type: Starting location of PTO2's profile table (byte offset from
V0)
System Manual, V2.3, 07/2017, A5E03822230-AF
S7-200 SMART

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-200 smart

Table of Contents