Loop table
The loop table is 80 bytes long and has the format shown in the following table.
Offset
Field
0
Process variable (PV
4
Setpoint (SP
n
8
Output (M
)
n
12
Gain (K
)
C
16
Sample time (T
20
Integral time or reset (T
24
Derivative time or rate (T
28
Bias (MX)
32
Previous process variable
(PV
)
n-1
36 to 79
Reserved for auto-tuning variables. Refer to PID loop definition table (Page 582) for details.
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
Format
)
REAL
n
)
REAL
REAL
REAL
)
REAL
S
)
REAL
I
)
REAL
D
REAL
REAL
Type
Description
In
Contains the process variable, which must be scaled
between 0.0 and 1.0.
In
Contains the setpoint, which must be scaled be-
tween 0.0 and 1.0.
In/Out
Contains the calculated output, scaled between 0.0
and 1.0.
In
Contains the gain, which is a proportional constant.
Can be a positive or negative number.
In
Contains the sample time, in seconds. Must be a
positive number.
In
Contains the integral time or reset, in minutes. Must
be a positive number.
In
Contains the derivative time or rate, in minutes. Must
be a positive number.
In/Out
Contains the bias or integral sum value between 0.0
and 1.0.
In/Out
Contains the value of the process variable stored
from the last execution of the PID instruction.
Program instructions
7.9 PID
321