Siemens SIMATIC S7 System Manual page 728

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

Technical specifications
A.3 Digital inputs and outputs expansion modules (EMs)
Table A- 75
Digital outputs
Model
Number of outputs
Type
Voltage range
Logic 1 signal at max. current
Logic 0 signal with 10 K Ω load
Rated current per point (max.)
Rated current per common
(max.)
Lamp load
ON state contact resistance
Leakage current per point
Surge current
Overload protection
Isolation (field side to logic)
Isolation resistance
Isolation between open contacts
Isolation groups
Inductive clamp voltage
Switching delay
Lifetime mechanical (no load)
Lifetime contacts at rated load
728
EM Digital
EM Digital
8 x Outputs
8 x Outputs Relay
(EM DT08)
(EM DR08)
8
8
Solid state -
Relay, dry contact
MOSFET (sourcing)
20.4 to 28.8 V DC
5 to 30 V DC or
5 to 250 V AC
20 V DC
-
0.1 V DC
-
0.75 A
2.0 A
3 A
8 A
5 W DC
30 W DC / 200 W
AC
0.6 Ω
0.2 Ω max. when
new
10 μA
--
8 A for 100 ms max. 7 A with contacts
closed
No
No
Optical, 500 V AC
1500 V AC for 1
for 1 minute
minute (coil to con-
tact)
None (coil to logic)
-
100 M Ω min. when
new
-
750 V AC for 1
minute
2
2
Minus 48 V DC, 1
-
W dissipation
Switch on less than
10 ms max.
50 μs and switch off
less than 200 μS
--
10,000,000
open/close cycles
--
100,000 open/close
cycles
EM Digital
EM Digital
16 x Outputs Relay
16 x Outputs Transis-
(EM QR16)
tor (EM QT16)
16
16
Relay, dry contact
Solid state -
MOSFET (sourcing)
5 to 30 V DC or
20.4 to 28.8 V DC
5 to 250 V AC
-
20 V DC
-
0.1 V DC
2.0 A
0.75 A
8 A
3 A
30 W DC/200 W AC 5 W
0.2 Ω max. when
0.6 Ω max.
new
--
10 μA
7 A with contacts
8 A for 100 ms max.
closed
No
No
1500 V AC for 1
500 V AC for 1 mi-
minute (coil to con-
nute
tact)
None (coil to logic)
100 M Ω min. when
-
new
750 V AC for 1
-
minute
4
4
-
L+ minus 48 V, 1 W
dissipation
10 ms max.
Switch on less than
50 μs and switch off
less than 200 μS
10,000,000
-
open/close cycles
100,000 open/close
-
cycles
System Manual, V2.3, 07/2017, A5E03822230-AF
S7-200 SMART

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-200 smart

Table of Contents