Divergence of a control stream, depending on transition conditions
In other situations, a control stream might be directed into one of several possible control
streams, depending upon which transition condition becomes true first.
Example: SCR divergent flow control, depending of transition conditions
LAD
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
Beginning of state L control region
Transition to state M
Transition to state N
End of SCR region for state L
STL
Network 1
LSCR S3.4
Network 2
LD M2.3
SCRT S3.5
Network 3
LD I3.3
SCRT S6.5
Network 4
SCRE
Program instructions