Siemens SIMATIC S7 System Manual page 194

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

Program instructions
7.3 Communication
Table 7- 4
Error codes for the GET and PUT instructions TABLE parameter
Code
Definition
0
No error
1
Illegal parameter in the PUT/GET table:
Local area is not I, Q, M, or V
Local area is not large enough for the data length requested
Data length is zero or greater than 222 bytes for a GET or greater than 212 bytes for a PUT
Remote area is not I, Q, M, or V
Remote IP address is illegal (0.0.0.0)
Remote IP address is a broadcast address or a multicast address
Remote IP address is the same as the Local IP address
Remote IP address is on a different subnet
2
Too many PUT/GET instructions are currently active (only 16 allowed)
3
No connection available. All connections are currently active with outstanding requests
4
Error returned from remote CPU:
Too much data was requested or sent
Writing to Q memory is not allowed in STOP mode
Memory area is write-protected (see SDB configuration)
5
No connection available to the remote CPU:
Remote CPU does not have an available server connection
Connection to remote CPU was lost (CPU powered off, physical disconnect)
6 to 9,
Not used (Reserved for future use)
A to F
194
System Manual, V2.3, 07/2017, A5E03822230-AF
S7-200 SMART

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-200 smart

Table of Contents