Configuration/Profile table
Byte off-
set
19
20
24
28
32
33
34
38
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
Name
Function description
--
Reserved: Set to 0
PLS/REV
Specifies the number of pulses per revolution of the
motor, (only applicable when MEAS_SYS is set to 1) -
(4 bytes)
UNITS/REV
Specifies the engineering units per revolution of the
motor, (only applicable when MEAS_SYS is set to 1) -
(4 bytes)
UNITS
Reserved for STEP 7-Micro/WIN SMART to store a
custom units string (4 bytes)
RP_CFG
Specifies the reference point search configuration
(1 byte):
RP_SEEK_DIR: This bit specifies the starting direction
for a reference point search (0 - positive direction, 1 -
negative direction).
RP_APPR_DIR: This bit specifies the approach direc-
tion for terminating the reference point search (0 -
positive direction, 1 - negative direction).
MODE
'0000'
'0001'
'0010'
'0011'
'0100'
'0101' to
'1111'
--
Reserved: Set to 0
RP_Z_CNT
Number of pulses of the ZP input used to define the
reference point (4 bytes)
RP_FAST
Fast speed for the RP seek operation: MAX_SPD or
less (4 bytes)
Configuration block
Specifies the reference point search meth-
od
Reference point search disabled.
The reference point is where the RPS
input goes active.
The reference point is centered within the
active region of the RPS input.
The reference point is outside the active
region of the RPS input.
The reference point is within the active
region of the RPS input.
Reserved (error if selected)
Open loop motion control
12.10 Advanced topics
Type
--
DInt
Real
--
--
--
DInt
DInt/Real
663