Sample Time And Update Times For The Analog Inputs; Measurement Ranges Of The Analog Inputs For Voltage And Current (Sb And Em) - Siemens SIMATIC S7 System Manual

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

A.4.5

Sample time and update times for the analog inputs

Table A- 111 Sample time and update time
Rejection frequency (Integra-
tion time)
400 Hz (2.5 ms)
60 Hz (16.6 ms)
50 Hz (20 ms)
10 Hz (100 ms)
A.4.6

Measurement ranges of the analog inputs for voltage and current (SB and EM)

Table A- 112 Analog input representation for voltage (SB and EM)
System
Decimal
Hexadecimal
32767
7FFF
1
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
AF00
-27648
9400
-27649
93FF
-32512
8100
-32513
80FF
-32768
8000
7FFF can be returned for one of the following reasons: overflow (as noted in this table), before valid values are available
1
(for example immediately upon a power up), or if a wire break is detected.
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
Sample time
4-channel SM: 0.625 ms
8-channel SM: 1.250 ms
4.170 ms
5.000 ms
25.000 ms
Voltage Measuring Range
±10 V
±5 V
11.851 V
5.926 V
11.759 V
5.879 V
10 V
5 V
7.5 V
3.75 V
361.7 μV
180.8 μV
0 V
0 V
-7.5 V
-3.75 V
-10 V
-5 V
-11.759 V
-5.879 V
-11.851 V
-5.926 V
A.4 Analog inputs and outputs expansion modules (EMs)
Module update time for all channels
4-channel SM
0.625 ms
4.17 ms
5 ms
25 ms
±2.5 V
±1.25 V
2.963 V
1.481 V
2.940 V
1.470 V
2.5 V
1.250 V
1.875 V
0.938 V
90.4 μV
45.2 μV
0 V
0 V
-1.875 V
-0.938 V
-2.5 V
-1.250 V
-2.940 V
-1.470 V
-2.963 V
-1.481 V
Technical specifications
8-channel SM
1.250 ms
4.17 ms
5 ms
25 ms
Overflow
Overshoot range
Rated range
Undershoot range
Underflow