Siemens SIMATIC S7 System Manual page 609

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

Note
High-speed input wiring must use shielded cables
Use shielded cable with a maximum length of 50 m, when connecting HSC input channels
I0.0, I0.1, I0.2, and I0.3.
Mapping the I/O
STEP 7-Micro/WIN SMART enforces a fixed output assignment for PWM and Axis of Motion.
P0 and P1 outputs
At a minimum, any axis that is enabled has a P0 output pin configured for it. It may also have
P1 output if its "Phase" configuration is anything other than "Single-phase (1 output)". Refer
to the "Editing default input and output configuration" section for more information. These
output pins are hard-coded to a specific output, depending on the following criteria:
Axis 0
Axis 1
Axis 2
DIS outputs
If an axis has a DIS output configured, then an entry is present in the mapping table for that
output. The DIS output is also hard-coded to specific outputs based upon the following rules:
● DIS for Axis 0 is always configured for Q0.4.
● DIS for Axis 1 is always configured for Q0.5.
● DIS for Axis 2 is always configured for Q0.6.
Pulse output units are connected to standard 24V outputs.
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
P0 for Axis 0 is always configured for Q0.0.
P1 for Axis 0 is configured for Q0.2 if the "Phase" for the axis is not configured to
"Single phase (1 output)".
P0 for Axis 1 is always configured for Q0.1.
P1 for Axis 1 is mapped in two possible locations based upon axis configuration as
follows:
If the "Phase" for Axis 1 is configured for "Single-phase (1 output)", then no P1
output is assigned.
If the "Phase" for Axis 1 is configured for "Two-phase (2 output)" or "AB quadra-
ture phase (2 output)", then P1 is configured for Q0.3.
Else, P1 for Axis 1 is configured for Q0.7.
P0 for Axis 2 is always configured for Q0.3.
P1 for Axis 2 is configured for Q1.0 if the "Phase" for the axis is not configured to
"Single phase (1 output)".
Axis 2 is not available for use if the configured "Phase" for Axis 1 is configured to
"Two-phase (2 output)" or "AB quadrature phase (2 output)".
Open loop motion control
12.5 Configuring an Axis of Motion
609