7.12.2

Block move

LAD / FBD
STL
BMB IN, OUT,
N
BMW IN, OUT,
N
BMD IN, OUT,
N
Non-fatal errors with ENO = 0
0006H Indirect address
0091H Operand out of range
Input / output
Data type
IN
BYTE
WORD, INT
DWORD, DINT
OUT
BYTE
WORD, INT
DWORD, DINT
N
BYTE
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
Description
The Block Move Byte, Block Move Word, and Block Move Double Word instruc-
tions move an assigned block of data values from a source memory location
(starting address IN and successive addresses) to a new memory location (start-
ing address OUT and successive addresses). Parameter N assigns the number
of bytes, words, or double words to move. The block of data values stored in the
source location are not changed.
N has a range of 1 to 255.
SM bits affected
None
Operand
IB, QB, VB, MB, SMB, SB, LB, *VD, *LD, *AC
IW, QW, VW, MW, SMW, SW, T, C, LW, AIW, *VD, *LD, *AC
ID, QD, VD, MD, SMD, SD, LD, *VD, *LD, *AC
IB, QB, VB, MB, SMB, SB, LB, *VD, *LD, *AC
IW, QW, VW, MW, SMW, SW, T, C, LW, AQW, *VD, *LD, *AC
ID, QD, VD, MD, SMD, SD, LD, *VD, *LD, *AC
IB, QB, VB, MB, SMB, SB, LB, AC, Constant, *VD, *LD, *AC