1.8 E: Motor Parameters

E3: V/f Pattern for Motor 2

No.
Name
(Hex.)
E3-01
Motor 2 Control Mode
Selection
(0319)
E3-04
Motor 2 Maximum
Output Frequency
(031A)
E3-05
Motor 2 Maximum
Output Voltage
(031B)
E3-06
Motor 2 Base Frequency
(031C)
E3-07
Motor 2 Mid Point A
Frequency
(031D)
E3-08
Motor 2 Mid Point A
Voltage
(031E)
E3-09
Motor 2 Minimum
Output Frequency
(031F)
E3-10
Motor 2 Minimum
Output Voltage
(0320)
E3-11
Motor 2 Mid Point B
Frequency
(0345)
Expert
E3-12
Motor 2 Mid Point B
Voltage
(0346)
Expert
E3-13
Motor 2 Base Voltage
(0347)
Expert

E4: Motor 2 Parameters

No.
Name
(Hex.)
E4-01
Motor 2 Rated Current
(0321)
E4-02
Motor 2 Rated Slip
(0322)
E4-03
Motor 2 Rated No-Load
Current
(0323)
E4-04
Motor 2 Motor Poles
(0324)
46
V/f
CL-V/f
OLV
CLV
AOLV
Sets the control method for motor 2.
Note:
When you change this setting, the drive will set all parameters that are dependent on
this parameter to their default settings.
0 : V/f Control
1 : V/f Control with Encoder
2 : Open Loop Vector
3 : Closed Loop Vector
V/f
CL-V/f
OLV
CLV
AOLV
Set the maximum output frequency for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the maximum output voltage for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the base frequency for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a middle output frequency for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a middle output voltage for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum output frequency for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum output voltage for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a middle output frequency for the motor 2 V/f pattern. Set this parameter to adjust the
V/f pattern for the constant output range. Usually it is not necessary to change this
parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a middle output voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/
f pattern for the constant output range. Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f
pattern for the constant output range. Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated current for motor 2 in amps.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated slip for motor 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the no-load current for motor 2 in amps when operating at the rated frequency and the
no-load voltage.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of poles for motor 2.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
Ref.
(Range)
0
306
(0 - 3)
Determined by E3-01
306
(40.0 - 590.0 Hz)
Determined by E3-01
307
(200 V Class: 0.0 - 255.0
V,
400 V Class: 0.0 - 510.0
V)
Determined by E3-01
307
(0.0 - E3-04)
Determined by E3-01
307
(0.0 - E3-04)
Determined by E3-01
307
(200 V Class: 0.0 - 255.0
V,
400 V Class: 0.0 - 510.0
V)
Determined by E3-01
307
(0.0 - E3-04)
Determined by E3-01
307
(200 V Class: 0.0 - 255.0
V,
400 V Class: 0.0 - 510.0
V)
0.0 Hz
307
(0.0 - E3-04)
0.0 V
308
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to
510.0 V)
0.0 V
308
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to
510.0 V)
Default
Ref.
(Range)
Determined by o2-04,
308
C6-01
(10% to 200% of the
drive rated current)
Determined by o2-04,
308
C6-01
(0.000 - 20.000 Hz)
Determined by o2-04,
309
C6-01
(Less than 0 - E4-01)
4
309
(2 - 120)

Advertisement