Safety Functions Integrated in the Drive
4.5 Control via terminals on the Control Unit and the power unit
NCU X122.4
DI x
r0722.x
M
Monitoring channel
Control Unit
Monitoring channel
Motor Module
Fig. 4-2
Terminals for "Safe Torque Off": example for Motor Modules, booksize format
Grouping drives
If the function is to be simultaneously initiated for several drives, the terminals for
the corresponding drives must be grouped together:
S 1st Control Unit shutdown path
By appropriately interconnecting the binector input to a joint input terminal for
the drives to be combined to form a group.
S 2nd Motor Module shutdown path
By appropriately connecting terminal "EP" for the individual Motor Modules be-
longing to a group.
Note
The grouping must be identical in both monitoring channels.
If a fault in a drive results in a Safe Torque Off (STO), this does not automatically
mean that the other drives in the same group also switch to Safe Torque Off
(STO).
The assignment is checked while testing the shutdown paths. The operator selects
Safe Torque Off for each group. The check is drive–specific.
4-66
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) – 05.2008 Edition
NCU 7x0
DRIVE–CLiQ
BI:
p9620
X21/X22
1
2
3
4
Motor Module
DRIVE–CLiQ
DRIVE–CLiQ
U2
V2
Temp+
W2
Temp–
BR+
EP +24 V
BR–
EP M
© Siemens AG 2008 All Rights Reserved