Siemens SINUMERIK 840D sl Function Manual page 526

Hide thumbs Also See for SINUMERIK 840D sl:
Table of Contents

Advertisement

Diagnostics
10.2 NCK safety alarms for SINUMERIK 840D sl
27201
Parameter
Explanation
Response
Remedy
Program
continuation
27202
Parameter
Explanation
Response
Remedy
Program
continuation
27203
Parameter
Explanation
10-526
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) – 05.2008 Edition
PROFIsafe: MD %1[%2]: Bus segment %3 error
%1 = MD name
%2 = MD field index
%3 = parameterized bus segment
An incorrect bus segment was entered in the specified machine data.
The value must be 5.
Mode group not ready
Channel not ready
NC start inhibit in this channel
Interface signals are set
Alarm display
NC stop for alarm
Correct the specified MD.
The alarm is initiated when booting. No program can be started. Only
delete the alarm with a power on.
PROFIsafe: MD %1[%2]: Address %3 error
%1 = MD name
%2 = MD field index
%3 = parameterized PROFIsafe address
The PROFIsafe address, parameterized in the specified MD is incorrect.
Mode group not ready
Channel not ready
NC start inhibit in this channel
Interface signals are set
Alarm display
NC stop for alarm
Correct the MD.
The alarm is initiated when booting. No program can be started. Only
delete the alarm with a power on.
PROFIsafe: MD %1[%2]: Incorrect SPL assignment
%1 = MD name
%2 = MD field index
The parameterization in the specified MD for the connection between
the SPL interface and a PROFIsafe module is incorrect. The reasons
for this are as follows:
– Bit limits interchanged (upper bit value < lower bit value)
– Bit values greater than in the definition of the SPL interface (bit
value> 64)
– Number of bits too high for this PROFIsafe module (upper bit value
– lower bit value > 8)
– No SPL assignment was parameterized (both bit values are equal to
zero)
– Incorrect SPL assignment (bit value equal to zero)