Safety Functions Integrated in the System/Drive
6.3 Safe Stops A–F
6.3.8

Forced checking procedure of the external STOPs

The following applies for the test stop of external STOPs:
All stop SGEs that are used are switched one after the other in each channel and
the positive response evaluated using the associated SGA "STOP x is active".
Note
Only the enabled and activated external standstill functions have to be tested.
SGE "deselect ext. STOP E"
SGA "STOP E is active"
SGE "deselect ext. STOP D"
SGA "STOP D is active"
SGE "deselect ext. STOP C"
Fig. 6-9
Sequence of the test stop for external STOPs. Example: External STOPs A, C, D, E are used
6-142
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) – 05.2008 Edition
SGA "STOP C is active"
SGE "deselect ext. STOP A"
SGA "STOP A/B is active"
© Siemens AG 2008 All Rights Reserved