B.1 A: Initialization Parameters
B.1 A: Initialization Parameters
Symbol
Parameter can be changed during run.
Refers to a second motor when the drive is operating two motors. Use multi-function input terminals to switch
Motor 2
between motors.
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
u

A1: Initialization

No.
(Addr.
Name
Hex)
A1-00
(100)
Language Selection
<1>
A1-01
(101)
Access Level Selection
<2>
A1-02
(102)
Control Method Selection
<1>
A1-03
Initialize Parameters
(103)
A1-04
Password
(104)
A1-05
Password Setting
(105)
A1-06
Application Preset
(127)
A1-07
DriveWorksEZ Function
(128)
Selection
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Application Preset selected with parameter A1-06.
176
Table B.1 Symbols and Icons Used in Parameter Descriptions
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
0: View and set A1-01 and A1-04. Uo-ooparameters can also be viewed.
1: User Parameters (access to a set of parameters selected by the user, A2-01
to A2-32)
2: Advanced Access (access to view and set all parameters)
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
Note: PM motor control modes are not available on 600 V class drives,
CIMR-Ao5oooooo.
0: No initialization
1110: User Initialize (parameter values must be stored using parameter o2-03)
2220: 2-Wire initialization
3330: 3-Wire initialization
5550: oPE04 error reset
When the value set into A1-04 does not match the value set into A1-05,
parameters A1-01 through A1-03, A1-06, and A2-01 through A2-33 cannot
be changed.
When the value set into A1-04 does not match the value set into A1-05,
parameters A1-01 through A1-03, A1-06, and A2-01 through A2-33 cannot
be changed.
0: General-purpose
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
0: DWEZ Disabled
1: DWEZ Enabled
2: Digital input (enabled when H1-oo = 9F)
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Description
Description
Values
Page
Default: 0
Range: 0 to 7
Default: 2
Range: 0 to 2
Default: 2
Range: 0 to 3;
88
5 to7
Default: 0
Range: 0 to 3330;
88
5550
Default: 0000
Min.: 0000
Max.: 9999
Default: 0000
Min.: 0000
Max.: 9999
Default: 0
Range: 0 to 5
Default: 0
Range: 0 to 2