B.6 F: Options
B.6 F: Options
F parameters program the drive for PG feedback from the motor and to function with option cards.
u

F1: PG Speed Control Card (PG-X3/PG-B3)

Parameters F1-01, F1-05, F1-06, F1-12, F1-13, and F1-18 through F1-21 include "PG 1" in the parameter name and are used
to set up a PG option card plugged into option port CN5-C of the drive.
Parameters F1-21 through F1-37 include "PG 2" in the parameter name and are used to set up a PG option card plugged into
option port CN5-B of the drive.
Other parameters in the F1 group are used to set operation for PG options plugged into port CN5-C and CN5-B.
No.
(Addr.
Name
Hex)
F1-01
PG 1 Pulses Per Revolution
(380)
F1-02
Operation Selection at PG
(381)
Open Circuit (PGo)
F1-03
Operation Selection at
(382)
Overspeed (oS)
F1-04
Operation Selection at
(383)
Deviation
F1-05
PG 1 Rotation Selection
(384)
F1-06
PG 1 Division Rate for PG
(385)
Pulse Monitor
F1-08
Overspeed Detection Level
(387)
F1-09
Overspeed Detection Delay
(388)
Time
F1-10
Excessive Speed Deviation
(389)
Detection Level
F1-11
Excessive Speed Deviation
(38A)
Detection Delay Time
F1-12
PG 1 Gear Teeth 1
(38B)
F1-13
PG 1 Gear Teeth 2
(38C)
F1-14
PG Open-Circuit Detection
(38D)
Time
198
Sets the number of PG (pulse generator or encoder) pulses. Sets the number
of pulses per motor revolution.
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
4: No alarm display
Note: Due to potential damage to the motor and machinery, only use the
"Alarm only" and "No alarm display" settings under special
circumstances.
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
0: Pulse A leads
1: Pulse B leads
Sets the division ratio for the pulse monitor used of the PG option card installed
to port CN5-C.
By setting "xyz", the division ratio becomes = [(1 + x) / yz].
If only using the A pulse for one-track input, the input ratio will be 1:1
regardless of F1-06 setting.
Sets the overspeed detection level as a percentage of the maximum output
frequency.
Sets the time in seconds for an overspeed situation to trigger a fault (oS).
Sets the speed deviation detection level as a percentage of the maximum output
frequency.
Sets the time in seconds for a speed deviation situation to trigger a fault (dEv). Default: 0.5 s
Sets the gear ratio between the motor shaft and the encoder (PG).
A gear ratio of 1 will be used if F1-12 or F1-13 are set to 0.
Sets the gear ratio between the motor shaft and the encoder (PG). A gear ratio
of 1 will be used if F1-12 or F1-13 are set to 0.
Sets the time required to trigger a PG Open fault (PGo).
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Description
Values
Page
Default: 1024 ppr
Min.: 1
Max.: 60000
Default: 1
Range: 0 to 4
Default: 1
Range: 0 to 3
Default: 3
Range: 0 to 3
<1>
Default:
Range: 0, 1
Default: 1
Min.: 1
Max.: 132
Default: 115%
Min.: 0
Max.: 120
<1>
Default:
Min.: 0.0 s
Max.: 2.0 s
Default: 10%
Min.: 0
Max.: 50
Min.: 0.0
Max.: 10.0
Default: 0
Min.: 0
Max.: 1000
Default: 0
Min.: 0
Max.: 1000
Default: 2.0 s
Min.: 0.0
Max.: 10.0