4.6 Basic Drive Setup Adjustments
No.
H4-02
Multi-Function Analog Output Terminal FM Gain
H4-03
Multi-Function Analog Output Terminal FM Bias
H4-05
Multi-Function Analog Output Terminal AM Gain
H4-06
Multi-Function Analog Output Terminal AM Bias
Using Gain and Bias to Adjust Output Signal Level
When viewing a gain setting parameter (H4-02 or H4-05) on the digital operator, the analog output will supply a voltage signal
equal to 100% of the monitor value (including changes made from bias and gain settings). When viewing a bias setting
parameter (H4-03 or H4-06), the analog output voltage will supply a signal equal to 0% monitor value.
Example 1: Set H4-02 to 50% for an output signal of 5 V at terminal FM when the monitored value is at 100%.
Example 2: Set H4-02 to 150% for an output signal of 10 V at terminal FM when the monitored value is at 76.7%.
10 V
Output Voltage
5 V
0 V
0%
Example 3: Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.
10 V
Output Voltage
3 V
0 V
0%
n
H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
Set jumper S5 on the terminal board accordingly when changing these parameters.
Selection on page 69
for details on setting S5.
No.
H4-07
H4-08
110
Name
H4-07, 08 = 0
Gain 150%
Bias 0%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
100%
Monitor Value
Figure 4.28 Analog Output Gain and Bias Setting Example 1 and 2
H4-07, 08 = 0
Bias 30%
Gain 100%
Bias 0%
Gain 100%
100%
Monitor Value
Figure 4.29 Analog Output Gain and Bias Setting Example 3
Name
Multi-Function Analog Output Terminal FM
Signal Level Selection
Multi-Function Analog Output Terminal AM
Signal Level Selection
Output Voltage
-100%
Output Voltage
-100%
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
H4-07, 08 = 1
15 V
Gain = 150%
Bias = 0%
10 V
Gain = 100%
Bias = 0%
5 V
Gain = 50%
Bias = 0%
100%
Monitor Value
-5 V
-10 V
-15 V
Gain = 100%
H4-07, 08 = 1
Bias = 30%
10V
Gain = 100%
Bias = 0%
3 V
100%
Monitor Value
-4 V
-10 V
Refer to Terminal AM/FM Signal
Setting Range
0 to 2
0 to 2
Default
100.0%
0.0%
50.0%
0.0%
Default
0
0