H4: Analog Outputs - YASKAWA A1000 Technical Manual

Hide thumbs Also See for A1000:
Table of Contents

Advertisement

H3-oo
Function
Setting
0
Frequency bias
1
Frequency gain
Auxiliary frequency reference 1
2
(used as a Multi-Step Speed 2)
Auxiliary frequency reference 2
3
(3rd step analog)
4
Output voltage bias
5
Accel/decel time gain
6
DC Injection Braking current
Overtorque/undertorque
7
detection level
8
Stall Prevention level during run
9
Output frequency lower limit level
B
PID feedback
C
PID setpoint
D
Frequency bias
E
Motor temperature (PTC input)
F
Through mode
10
Forward torque limit
11
Reverse torque limit
12
Regenerative torque limit
13
Torque reference/Torque limit
14
Torque compensation
15
General torque limit
16
Differential PID feedback
17
Motor Thermistor (NTC)
1F
Through mode
DriveWorksEZ
30 to 32
analog input 1 to 3
u

H4: Analog Outputs

No.
(Addr.
Name
Hex)
Multi-Function Analog
H4-01
Output Terminal FM
(41D)
Monitor Selection
H4-02
Multi-Function Analog
(41E)
Output Terminal FM Gain
H4-03
Multi-Function Analog
(41F)
Output Terminal FM Bias
Multi-Function Analog
H4-04
Output Terminal AM
(420)
Monitor Selection
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
H3 Multi-Function Analog Input Settings
10 V = E1-04 (maximum output frequency)
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting of -100
to 0%.
10 V = E1-04 (maximum output frequency)
10 V = E1-04 (maximum output frequency)
10 V = E1-05 (motor rated voltage)
10 V = 100%
10 V = Drive rated current
10 V = Drive rated current (V/f, V/f w PG)
10 V = Motor rated torque (OLV, CLV, OLV/PM, AOLV/PM, CLV/PM)
10 V = Drive rated current
10 V = E1-04 (maximum output frequency)
10 V = 100%
10 V = 100%
10 V = E1-04 (maximum output frequency)
10 V = 100%
Set this value when using the terminal in the pass-through mode.
10 V = Motor rated torque
10 V = Motor rated torque
10 V = Motor rated torque
10 V = Motor rated torque
10 V = Motor rated torque
10 V = Motor rated torque
10 V = 100%
10 V = -9 °C
0 V = 234 °C
Note: This function is only available in models CIMR-Ao4A0930 and 4A1200.
Set this value when using the terminal in the pass-through mode.
Output is determined by the function selected using DWEZ.
Description
Selects the data to be output through multi-function analog output terminal
FM.
Set the desired monitor parameter to the digits available in Uo-oo.
For example, enter "103" for U1-03.
Sets the signal level at terminal FM that is equal to 100% of the selected
monitor value.
Sets the signal level at terminal FM that is equal to 0% of the selected monitor
value.
Selects the data to be output through multi-function analog output terminal
AM.
Set the desired monitor parameter to the digits available in Uo-oo.
For example, enter "103" for U1-03.
B.7 H Parameters: Multi-Function Terminals
Description
Page
Values
Page
Default: 102
109
Range: 000 to 999
Default: 100.0%
Min.: -999.9
109
Max.: 999.9
Default: 0.0%
Min.: -999.9
109
Max.: 999.9
Default: 103
109
Range: 000 to 999
211
B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents