YASKAWA A1000 Technical Manual page 246

Hide thumbs Also See for A1000:
Table of Contents

Advertisement

C.2 UL and CSA Standards
Terminal
Wire Gauge
Screws
M6
2
22 mm
M8
4 AWG
M10
M8
2
30 / 38 mm
3 / 2 AWG
M10
2
M8
50 / 60 mm
1 AWG
1/0 AWG
M10
1/0 AWG × 2P
1 AWG × 2P
M10
2 AWG × 2P
2
80 mm
M10
2/0 / 3/0 AWG
2/0 AWG × 2P
M10
3/0 AWG × 2P
3/0 AWG × 4P
M12
2
100 mm
M10
4/0 AWG
M10
4/0 AWG × 2P
4/0 AWG × 4P
M12
M10
2
150 mm
250 / 300 kcmil
M12
250 kcmil × 2P
M10
250 kcmil × 4P
300 kcmil × 2P
M12
300 kcmil × 4P
2
M10
200 mm
350 kcmil
M12
400 kcmil
350 kcmil × 2P
M12
400 kcmil × 2P
2
M10
325 mm
500 kcmil
600 / 650 kcmil
M12
500 kcmil × 2P
600 kcmil × 2P
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable temperature
of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
Input Fuse Installation
Always install fuses at the drive input side.
246
Crimp Terminal
Model Number
Machine No.
R22-6
YA-5
R22-8
YA-5
R22-10
YA-5
R38-8
YA-5
R38-10
YA-5
R60-8
YA-5
R60-10
YF-1, YET-300-1
38-L10
YF-1, YET-150-1
80-10
YF-1, YET-300-1
80-L10
YF-1, YET-150-1
80-L12
YF-1, YET-300-1
YF-1, YET-300-1
R100-10
YF-1, YET-150-1
100-L10
YF-1, YET-150-1
100-L12
YF-1, YET-300-1
R150-10
YF-1. YET-150-1
R150-12
YF-1, YET-300-1
150-L10
YF-1, YET-150-1
150-L12
YF-1, YET-300-1
200-10
YF-1, YET-300-1
R200-12
YF-1, YET-300-1
200-L12
YF-1, YET-300-1
325-10
YF-1, YET-300-1
325-12
YF-1, YET-300-1
Refer to Installing Fuses on the Input Side on page 238
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Tool
Die Jaw
AD-953
AD-953
AD-953
AD-954
AD-954
AD-955
TD-321, TD-311
TD-224, TD-212
TD-323, TD-312
TD-227, TD-214
TD-323, TD-312
TD-324, TD-312
TD-228, TD-214
TD-228, TD-214
TD-324, TD-312
TD-229, TD-215
TD-325, TD-313
TD-229, TD-215
TD-325, TD-313
TD-327, TD-314
TD-327, TD-314
TD-327, TD-314
TD-328, TD-315
TD-328, TD-315
Insulation
<1>
Cap
Code
Model No.
TP-022
100-051-262
TP-022
100-051-263
TP-022
100-061-113
TP-038
100-051-264
TP-038
100-061-114
TP-060
100-051-265
TP-060
100-051-266
TP-038
100-051-556
TP-080
100-051-267
TP-080
100-051-557
TP-080
100-051-558
TP-100
100-051-269
TP-100
100-051-559
TP-100
100-051-560
TP-150
100-051-272
TP-150
100-051-273
TP-150
100-051-561
TP-150
100-051-562
TP-200
100-051-563
TP-200
100-051-275
TP-200
100-051-564
TP-325
100-051-565
TP-325
100-051-277
for selecting fuses.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents