U3: Fault History

No.
(Addr.
Name
Hex)
U3-01 to
U3-04
First to 4th Most Recent
(90 to 93
Fault
(800 to
803))
U3-05 to
U3-10
5th to 10th Most Recent
(804 to
Fault
809)
U3-11 to
U3-14
Cumulative Operation
(94 to 97
Time at 1st to 4th Most
(80A to
Recent Fault
80D))
U3-15 to
Cumulative Operation
U3-20
Time at 5th to 10th Most
(80E to
Recent Fault
813)
u

U4: Maintenance Monitors

No.
(Addr.
Name
Hex)
U4-01
Cumulative Operation
(4C)
Time
U4-02
Number of Run
(75)
Commands
U4-03
Cooling Fan Operation
(67)
Time
U4-04
Cooling Fan Maintenance
(7E)
U4-05
Capacitor Maintenance
(7C)
U4-06
Soft Charge Bypass Relay
(7D6)
Maintenance
U4-07
IGBT Maintenance
(7D7)
U4-08
Heatsink Temperature
(68)
U4-09
LED Check
(5E)
U4-10
kWh, Lower 4 Digits
(5C)
U4-11
kWh, Upper 5 Digits
(5D)
U4-13
Peak Hold Current
(7CF)
U4-14
Peak Hold Output
(7D0)
Frequency
U4-16
Motor Overload Estimate
(7D8)
(oL1)
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Description
Displays the first to the fourth most recent faults.
Displays the fifth to the tenth most recent faults.
After ten faults, data for the oldest fault is deleted. The most recent fault
appears in U3-01, with the next most recent fault appearing in U3-02. The
data is moved to the next monitor parameter each time a fault occurs.
Displays the cumulative operation time when the first to the fourth most
recent faults occurred.
Displays the cumulative operation time when the fifth to the tenth most
recent faults occurred.
Description
Displays the cumulative operation time of the drive. The value for the
cumulative operation time counter can be reset in parameter o4-01. Use
parameter o4-02 to determine if the operation time should start as soon as
the power is switched on or only while the Run command is present. The
maximum number displayed is 99999, after which the value is reset to 0.
Displays the number of times the Run command is entered. Reset the
number of Run commands using parameter o4-13. This value will reset to
0 and start counting again after reaching 65535.
Displays the cumulative operation time of the cooling fan. The default value
for the fan operation time is reset in parameter o4-03. This value will reset
to 0 and start counting again after reaching 99999.
Displays main cooling fan usage time as a percentage of its expected
performance life. Parameter o4-03 can be used to reset this monitor.
Displays main circuit capacitor usage time as a percentage of their expected
performance life. Parameter o4-05 can be used to reset this monitor.
Displays the soft charge bypass relay maintenance time as a percentage of
its estimated performance life. Parameter o4-07 can be used to reset this
monitor.
Displays IGBT usage time as a percentage of the expected performance
life. Parameter o4-09 can be used to reset this monitor.
Displays the heatsink temperature.
Lights all segments of the LED to verify that the display is working
properly.
Monitors the drive output power. The value is shown as a 9-digit number
displayed across two monitor parameters, U4-10 and U4-11.
Example:
12345678.9 kWh is displayed as:
U4-10: 678.9 kWh
U4-11: 12345 MWh
Displays the highest current value that occurred during run.
Displays the output frequency when the current value shown in U4-13
occurred.
Shows the value of the motor overload detection accumulator. 100% is
equal to the oL1 detection level.
B.13 U: Monitors
Analog Output
Unit
Level
No signal output
available
No signal output
available
No signal output
1 h
available
No signal output
1 h
available
Analog Output
Unit
Level
No signal output
1 h
available
No signal output
1 Time
available
No signal output
1 h
available
No signal output
1%
available
No signal output
1%
available
No signal output
1%
available
No signal output
1%
available
10 V: 100 °C
1 °C
No signal output
available
No signal output
1 kWh
available
No signal output
1 MWh
available
No signal output
0.01 A
available
<1> <2>
No signal output
0.01 Hz
available
10 V: 100%
0.1%
233