4.6 Basic Drive Setup Adjustments
Note: If b2-01 is set to a smaller value than parameter E1-09 (minimum frequency), then DC Injection Braking will begin as soon as the frequency
falls to the value set to E1-09.
OLV/PM and AOLV/PM (A1-02 = 5, 6)
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooo.
For these control modes, parameter b2-01 sets the starting frequency for Short-Circuit Braking at stop. When the output
frequency falls below the setting of b2-01, Short-Circuit Braking is enabled for the time set in parameter b2-13. If DC Injection
Braking time is enabled at stop, then DC Injection Braking is performed for the time set in b2-04 after Short-Circuit Braking
is complete.
Note: If b2-01 is set to a smaller value than parameter E1-09 (minimum frequency), then DC Injection Braking will begin as soon as the frequency
falls to the value set to E1-09.
CLV and CLV/PM (A1-02 = 3, 7)
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooo.
For these control modes, parameter b2-01 sets the starting frequency for Zero Speed Control (not position lock) at stop. When
the output frequency falls below the setting of b2-01, Zero Speed Control is enabled for the time set in parameter b2-04 provided
b1-05 is set to 0.
Note: If b2-01 is set lower than the minimum frequency (E1-09), then Zero Speed Control begins at the frequency set to E1-09.
n
b3-01: Speed Search Selection at Start
Determines if Speed Search is automatically performed when a Run command is issued.
No.
b3-01
Setting 0: Disabled
This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed
Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.
Setting 1: Enabled
This setting performs Speed Search when the Run command is entered. The drive begins running the motor once Speed Search
is complete.
94
Output
frequency
Figure 4.15 DC Injection Braking at Stop for V/f, V/f w/PG and OLV
E1-09 Min. Frequency
b2-01 Zero Speed Level
Output
frequency
Figure 4.16 Short-Circuit Braking at Stop in OLV/PM and AOLV/PM
E1-09 Min. Frequency
b2-01 Zero Speed Level
Output
frequency
Figure 4.17 Zero Speed Control at Stop in CLV and CLV/PM
Parameter Name
Speed Search Selection at Start
DC Injection
Braking
E1-09 Min. Frequency
b2-01 Zero Speed Level
b2-04
Short Circuit
Braking
b2-13
b2-04
Zero Speed
Control
b2-04
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Time
DC Injection
Braking
Time
Time
Setting Range
0, 1
Default
Determined by
A1-02