Note: If an overcurrent (oC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the fault no longer
occurs.
Setting 3: Coast to Stop with Timer
When the Run command is removed, the drive will turn off its output and the motor will coast to stop. The drive will not start
if a Run command is input before the time t (C1-02) has expired. Cycle the Run command that was activated during time t
after t has expired to start the drive.
The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.
n
b2-01: DC Injection Braking Start Frequency
Active when "Ramp to Stop" is selected as the stopping method (b1-03 = 0).
No.
b2-01
The function triggered by parameter b2-01 depends on the control mode that has been selected.
V/f, V/f w/PG, and OLV (A1-02 = 0, 1, 2)
For these control modes, parameter b2-01 sets the starting frequency for DC Injection Braking at Stop. When the output
frequency falls below the setting of b2-01, DC Injection Braking is enabled for the time set in parameter b2-04.
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
DC Injection braking time
b2-04×10
b2-04
Output frequency when
10%
Stop command was entered
Figure 4.12 DC Injection Braking Time Depending on Output Frequency
Run command
ON
Output
frequency
Figure 4.13 Coast to Stop with Timer
Run wait time t
Active deceleration time
Min Baseblock Time (L2-03)
Min output
frequency
Figure 4.14 Run Wait Time Depending on Output Frequency
Name
DC Injection Braking Start Frequency
4.6 Basic Drive Setup Adjustments
100%
(Maximum output
frequency)
OFF
ON
OFF
ON
Drive output shut off
Run wait time t
100%
Output frequency
(Max output
when Stop command
frequency)
was entered
Setting Range
0.0 to 10.0 Hz
4
Default
Determined by
A1-02
93