Remote I/O Error Information [Bfm #8 (8H) To #11 (Bh)]; Reserved Station Information [Bfm #16 (10H) To #19 (13H)]; Number Of Required Input Blocks [Bfm #20 (14H)]; Power - Mitsubishi FX3UC SERIES User Manual

Hide thumbs Also See for FX3UC SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3UC
User's Manual - Hardware Edition
3. CONFIG mode (Cautions on use)
In CONFIG mode, if the detailed remote station information [BFM #32 (20h) to #95 (5Fh)] is edited, and if the
detailed remote station information is inconsistent with remote stations actually connected at the time of
power ON as a result of the editing, there will be a data link error.
(When BFM #32 (20h) to #95 (5Fh) is edited, the station numbers are checked.)
If the power is set to ON while all remote stations are unconnected or if remote stations are disconnected
after the power was set to ON, data link error is not detected, as long as the detailed remote station
information is not edited.

9.18.3 Remote I/O error information [BFM #8 (8h) to #11 (Bh)]

The remote I/O error occurrence status is stored here. (Bits for stations with I/O error are ON.)
For the type of error, refer to the instruction manual of each remote station.
1. Detailed description
The station number of each remote station is assigned to each bit of the buffer memory [BFM #8 (8h) to #11
(Bh)]. The absence/presence of remote I/O errors are indicated by the 0 (OFF)/1 (ON) status of each bit.
Buffer
memory No.
BFM #8 (0h)
Station No.16 Station No.15 Station No.14
BFM #9 (1h)
Station No.32 Station No.31 Station No.30
BFM #10 (2h) Station No.48 Station No.47 Station No.46
BFM #11 (3h) Station No.64 Station No.63 Station No.62

9.18.4 Reserved station information [BFM #16 (10h) to #19 (13h)]

Station numbers specified as reserved stations are stored here. (Bits for reserved stations are ON.)
1. Detailed description
The station number of each remote station is assigned to each bit of the buffer memory [BFM #16 (10h) to
#19 (13h)]. Whether or not a station is specified as reserved is indicated by the 0 (OFF)/1 (ON) status of each
bit.
Buffer
memory No.
BFM #16 (0h) Station No.16 Station No.15 Station No.14
BFM #17 (1h) Station No.32 Station No.31 Station No.30
BFM #18 (2h) Station No.48 Station No.47 Station No.46
BFM #19 (3h) Station No.64 Station No.63 Station No.62
2. Specify reserved stations
Specify reserved stations by editing the detailed remote station information [BFM #32 (20h) to 95 (5Fh)] in
CONFIG mode.

9.18.5 Number of required input blocks [BFM #20 (14h)]

The number of input blocks (8 points/block) required to assign the I/O numbers of remote stations is stored
here.
→ For details on the specification of a reserved station, refer to Section 9.12.
b15
b14
b15
b14
→ For details specification of reserved station, refer to Section 9.12.
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
0 (OFF): Remote I/O error is absent
1 (ON): Remote I/O error is present
Bit
b13
•••
b2
•••
Station No.3
•••
Station No.19 Station No.18 Station No.17
•••
Station No.35 Station No.34 Station No.33
•••
Station No.51 Station No.50 Station No.49
0 (OFF): The station is not specified as a reserved one.
1 (ON): The station is specified as a reserved one.
Bit
b13
•••
b2
•••
Station No.3
•••
Station No.19 Station No.18 Station No.17
•••
Station No.35 Station No.34 Station No.33
•••
Station No.51 Station No.50 Station No.49
9.18 Details of buffer memory
Initial value: 0 (OFF)
b1
b0
Station No.2
Station No.1
Initial value: 0 (OFF)
b1
b0
Station No.2
Station No.1
311
1
2
3
4
5
6
7
8
9
10