2) Restriction for the 5V DC power supply capacity
Calculate the 5V DC power supply capacity for the main unit or extension power supply unit.
a)Supplier side
FX
-32MT-LT 350mA
3UC
b)Consumer side
FX
-32EX
2NC
FX
-32EX
2NC
FX
-32EYT
2NC
FX
-16EYR-T
2NC
FX
-16EYR-T
2NC
FX
-4AD
2NC
FX
-CNV-IF
2NC
FX
-10PG
2N
FX
-2LC
2N
FX
-16EYT
2N
"a)Supplier side" - "b)Consumer side" = 350mA - 740mA = -390mA
a) It is necessary to add an extension power supply unit since the capacity on the
consumer side b) is 390mA larger than the capacity on the supplier side a).
3) Restriction for the number of connectable units
a) Expansion board
There is no problem since this configuration does not include an expansion board.
b) Special function unit/block
This configuration includes the following 3 special function units/blocks.
There is no problem since up to 7 special function units/blocks can be connected.
-
FX
2NC
-
FX
2N
-
FX
2N
c) Other restriction
In some models, only 1 unit can be connected to the main unit.
When connecting 2 or more units, it is necessary to add the extension power supply unit. (Refer to
Subsection 1.10.2.)
This configuration includes the following equipment that falls under the restriction for the number of
connectable units.
-
FX
2NC
66
5V DC power supply capacity and current consumption
60mA
60mA
120mA
100mA
50mA
50mA
50mA
0mA
120mA
70mA
180mA
-4AD
-10PG
-2LC
-16EYR-T × 2
1.13 Selection Calculation Example 2 for System Configuration
220mA
270mA
320mA
370mA
490mA
560mA
740mA
NG!!
→ Refer to Subsection 1.13.1.
OK!!
OK!!
NG!!
→ Refer to Subsection 1.13.1.