Mitsubishi FX3UC SERIES User Manual page 272

Hide thumbs Also See for FX3UC SERIES:
Table of Contents

Advertisement

FX
FX
Series Programmable Controllers
Series Programmable Controllers
3UC
3UC
User's Manual - Hardware Edition
User's Manual - Hardware Edition
3. Selection of the general-purpose power supply connected to the Main unit
When using the CC-Link/LT master function, connect a general-purpose power supply that satisfies the
following condition to the main unit.
If the following conditions are not satisfied, for example, due to a change in the system, then changing the
general-purpose power supply or using a power adapter/dedicated power supply should be considered.
1) The power source must supply a minimum of 20.4V DC to the CC-Link/LT system for the I/O modules to
operate correctly.
Do not exceed the maximum input voltage (28.8V DC) of the power adapter.
20.4V + voltage drop
2) Select a general-purpose power supply whose rated output current can cope with the value required in
the current consumption calculation (9.6.3)
Rated output current of general-purpose power supply
stations that receive power from built-in power supply
3) Select a general-purpose power supply whose maximum output current
current value expected at the start-up of the CC-Link/LT system (when the power is turned on).
Maximum output current of general-purpose power supply
*1.
Maximum output current: May be referred to as "peak output current".
If there is no description concerning maximum output current, use the threshold value of the "high
current limiting function".
266
→ For the voltage drop calculation, refer to Subsection 9.6.3.
General purpose power supply output voltage
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
9.6 Selection of the power supply for CC-Link/LT
Total current consumption of remote I/O
*1
24V DC 30A, 0.5ms
28.8V
can cope with the calculated