10.20.4 Program example 2 (when 3 or fewer devices are displayed as user-registered devices)
Use this program example as a reference when setting 3 or fewer devices as user-registered devices.
1. Precaution When Setting 3 Or Fewer Devices
When 3 or fewer devices are set as user-registered devices, the "type" setting for unused devices should be
set to a value other than 7 and 8.
2. Operation
In this program example, the 3 devices shown in the table below are set as user-registered devices, with a
hexadecimal format specified for the current value display.
1) The hexadecimal display format applies only to current values which are displayed at the "user-registered
device" menu. Other current values are displayed in a decimal format.
2) In this program example, system information is assigned from D50 to D90 and from M50 to M56.
User-Registered Device
No.
1
2
3
3. Program
M8002
Initial pulse
M8002
Initial pulse
User-
registered
device
User message
monitoring
display command
in progress
M56
M54
User-
registered
device
User message
monitoring in
display command
progress
M56
M54
360
Devices Set As User-
Registered Devices
D100 (D101)
D102
D103
MOV
K50
D8300
MOV
K50
D8301
MOV
K8
D50
MOV
K100
D51
MOV
K7
D52
MOV
K102
D53
MOV
K7
D54
MOV
K103
D55
MOV
K-1
D56
MOV
K-1
D57
SET
M55
RST
M55
10 Display Module (Only FX3UC-32MT-LT)
10.20 User (User-Registered Device Setting)
Display
Data Length
Format
32-Bit
16-Bit
Hexadecimal
16-Bit
System information (system No.1) is set at D50 to D90.
System information (system No.2) is set at M50 to M56.
User-registered device 1 is set as 32-bit data at "D101, D100".
User-registered device 2 is set as 16-bit data at "D102".
User-registered device 3 is set as 16-bit data at "D103".
User-registered device 4 is not.
Hexadecimal current value appears while user-registered device
monitoring screen is displayed.
At other Monitor/Test screens, the current values and setting values
are displayed in a decimal format.