Use Of Several Running/Stopping Methods - Mitsubishi FX3UC SERIES User Manual

Hide thumbs Also See for FX3UC SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3UC
User's Manual - Hardware Edition
• FX
-
MT/D, FX
3UC
• FX
-
MT/DSS
3UC
24V DC
3. Starting and stopping by remote control from programming software
The programming software has a function to forcibly start and stop the PLC by remote control (remote RUN/
STOP function).
However, when power is reapplied, the remote RUN/STOP function is disabled. The RUN/STOP status is
then determined by the RUN/STOP switch or RUN terminal.
The remote operation for starting and stopping from the programming software is used in combination with
the built-in RUN/STOP switch.

12.2.2 Use of several running/stopping methods

1. When the built-in RUN/STOP switch and the general-purpose RUN terminal are used
(without remote running/stopping operation from the programming software)
The RUN/STOP status of the PLC is determined by the conditions shown in the following table.
Condition of built-in
RUN/STOP switch
RUN
STOP
Use either built-in RUN/STOP switch or the general input specified as RUN terminal.
(When specifying the general-purpose terminal as the RUN terminal, always set the built-in RUN/STOP
switch to STOP.)
2. When the remote running/stopping operation from the programming software is performed
For this operation, keep both the built-in RUN/STOP switch and the general-purpose input RUN terminal in
the STOP position.
If the stop command is given from the programming software after the PLC is started by either the built-in
RUN/STOP switch or the general-purpose input RUN terminal, the PLC will be restored to the running status
by giving the RUN command from the programming software. This can also be accomplished by setting the
built-in RUN/STOP switch or the general-purpose input RUN terminal to STOP and then to RUN.
386
-32MT-LT
3UC
PLC
RUN
STOP
PLC (sink input)
Condition of general-purpose input terminal
specified as RUN terminal by parameter
12 Test Operation, Adjustment, Maintenance and Troubleshooting
12.2 Running and Stopping Procedures [Power ON]
24V DC
OFF
ON
OFF
ON
RUN
STOP
PLC (source input)
Status of PLC
RUN
RUN
STOP
RUN