Mitsubishi FX3UC SERIES User Manual page 76

Hide thumbs Also See for FX3UC SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3UC
User's Manual - Hardware Edition
2. Judgment of system configuration availability
Note that the available maximum number of input/output points varies depending on the version of the
FX
-32MT-LT.
3UC
1) Restriction for the number of input/output points
Number of input / occupied output points
a) Main unit (Number of input / occupied output points) Total of a)
FX
-32MT-LT
3UC
b) I/O extension block
(Number of input / occupied output points)
FX
-32EX
2NC
FX
-32EYT
2NC
FX
-16EYR-T
2NC
FX
-16EYR-T
2NC
c) Expansion board, Special adapter
(Number of input / occupied output points)
FX
-232-BD
3U
FX
-485ADP(-MB)
3U
FX
-4AD-ADP
3U
d) Total number of input/output points in remote I/O
stations for built-in CC-Link/LT
CL1X4-D1B2
CL1Y4-T1B2
e) Special function units / blocks
(Number of input / occupied output points)
FX
-4AD
2NC
FX
-10PG
2N
FX
-2LC
2N
FX
-16CCL-M
2N
Total number of I/O points
The restriction for the number of input/output points is satisfied since the total number of
input/output points in
When the FX
Ver.2.20 or later
h) Number of input/output occupied points in remote I/O
stations in network (CC-Link)
AJ65BTB1-16D
AJ65BTB1-16T
Number of input/output occupied points in network
The restriction for the number of input/output points is satisfied since the total number of
input/output occupied points in the network is less than 224.
Total number of input/output occupied points + Total number
of input/output occupied points in network
The restriction for the number of input/output points is satisfied since the total number of
input/output points plus the total number of input/output occupied points in the network in
is less than 384.
70
32 points
32 points
32 points
16 points
16 points
0 points
0 points
0 points
4 points
4 points
8 points
8 points
8 points
*1
8 points
and
is less than 256.
-32MT-LT is Ver.2.20 or later, the following calculation is required.
3UC
1.14 Selection Calculation Example 3 for System Configuration
Ver.2.20 or less
Total of b)
32 + 32 + 16 + 16 = 96
Total of c)
0 + 0 + 0 =0
Total of d)
4 + 4 = 8 points
Total of e)
8 + 8 + 8 + 8 + 64
[Input/output occupied
points in remote
×
I/O (32points
2units)] = 96
a) + b) + c) + d) + e) = f)
32 + 96 + 8 + 96 = 232
f) < 256 points.................
32 points
32 points
Ver.2.20 or later
Total of a)
32 points
Total of b)
32 + 32 + 16+ 16 = 96
96 points
Total of c)
0 + 0 + 0 = 0
0 points
Total of d)
4 + 4 = 8 points
8 points
Total of e)
8 + 8 + 8 + 8 = 32
*1 Input/output occupied
points in remote I/O
stations are not included
in the calculation here.
96 points
a) + b) + c) + d) +e) = g)
32 + 96 + 8 + 32 = 168
g) < 256 points................
Total of h)
64 [Input/output occupied
points in remote I/O
-
×
(32points
2units)] = 64
64points
-
h) < 224points
g) + h) = i)
-
h) < 384points.................
1 Outline
32 points
96 points
0 points
8 points
32 points
OK!!
OK!!
OK!!

Advertisement

Table of Contents
loading