Selection Of The Power Supply For Cc-Link/Lt; System Power Calculation Procedure - Mitsubishi FX3UC SERIES User Manual

Hide thumbs Also See for FX3UC SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3UC
User's Manual - Hardware Edition
9.6

Selection of the power supply for CC-Link/LT

9.6.1

System power calculation procedure

Calculate the system power using the following procedure.
When the power supply adapter or dedicated power supply is required, refer to the appropriate manual for the
"current consumption" and "voltage drop" of the remote I/O stations connected to the power supply adapter/
dedicated power supply and later positions.
Calculation procedure
Design remote I/O station connection
configuration and wiring length design.
Calculate current consumption.
Refer to 9.6.3-1
Total current
consumption of remote I/O
stations that receive power
from built-in power
supply ≤ 0.35 A
Check simplified graph or calculate
voltage drop.
Refer to 9.6.3-2
Is voltage drop ≤ 3.6 V
Minimum operating voltage
(20.4 V) for each module shall be
assured.
Power supply voltage
- Voltage drop ≥ 20.4V
Select general-purpose power supply.
Refer to 9.6.3-3
Completed
Start
NO
YES
NO
YES
NO
YES
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
9.6 Selection of the power supply for CC-Link/LT
Check the built-in power supply again.
Examine the system using the power
supply adapter or dedicated power
supply.
Refer to Subsection 9.6.2.
For the power supply adapter or
dedicated power supply, refer to each
manual.
1
2
3
4
5
6
7
8
9
10
261