How To Attach Connectors For The Vctf Cable/High Flexible Cable (Terminal/T-Branch Processing) - Mitsubishi FX3UC SERIES User Manual

Hide thumbs Also See for FX3UC SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3UC
User's Manual - Hardware Edition
9.8.4
How to attach connectors for the VCTF cable/high flexible cable (terminal/T-branch
processing)
This section explains how to attach VCTF cable connectors and high flexible cable connectors.
1. Components
The components are shown below.
Component 1 : Cover
VCTF cable connector : Green
Flexible cable connector : Yellow green
2. Attachment procedure
The procedure is shown below.
1) Terminal processing procedure
Applicable attachment: Terminal resistor attachment at the trunk line end and terminal processing
1)
Correctly align the VCTF cable/
high flexible cable with the same
colored sections.
Component 2 : Body (Aqua)
2)
40mm
(1.57")
Green : Correct wiring
Red, white or black : Incorrect
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
9.8 Connection of Cables, Connectors and Terminating Resistors
Close the cover to firmly hold
the VCTF cable/high flexible
cable in place.
When the cable is correctly
wired, the green wire can be
seen from the notched window.
If the red, white or black wire is
seen from the notched window,
the wiring is wrong.
Open the cover, and correctly
set the cable.
Incorrect wiring causes failures
in the unit.
wiring
Component 3 : VCTF cable/
High flexible cable
Relationship between wire
color and signal
Signal name
Wire color
+24V
Red
DA
White
Black
DB
Green
24G
3)
Combine the body with the
cover, and press-fit them
with pliers, etc.
4)
Confirm that the latch is
engaged in four positions.
Now, press-fitting is finished.